5. Adjusting the bypass
Use the following procedure to adjust the bypass:
1.Valve 1 wide open. Valve 2 & valve 3 closed.
2.
Slowly open valve 2 & valve 3 by half, then close the valve 1 slowly to increase the water flow to valve 2
& valve 3.
3.
If it shows‘ON` or `EE3’ on the display, it means the water flow into the heat pump is not enough, then
you need to adjust the valves to increase the water flow through the heat pump.
How to get the optimum water flow:
Please turn on the heat pump under heating function, firstly close the by-pass then open it slowly to start the
heat pump (the machine can't start running when the water flow is insufficient).
Continue to adjust the by-pass slowly, at this time check the Inlet water temp. & Outlet water temp., it will be
optimum when the difference is around 2 degree.
Drain out the water in winter for the units without drainage outlet in heat exchanger
Turn off the heat pump and be sure that it is disconnected from
power Turn off the water pump
Summary of Contents for CHP075PX
Page 1: ......
Page 2: ...Please read and understand ALL the instructions before installation and use...
Page 6: ...4 2 Dimension unit mm 2 1 Model CHP075PX CHP095PX...
Page 7: ...5 2 2 Model CHP115PX CHP135PX CHP165PX 2 3 Model CHP205PX CHP255PX...
Page 8: ...6 2 4 Model CHP305PX...
Page 11: ...9 Dry contact timer connection Timer Dry contact pump connection Water pump...
Page 32: ...30 10 Exploded view 10 1 Model CHP075PX CHP095PX...
Page 34: ...32 10 2 Model CHP115PX CHP135PX CHP165PX...
Page 36: ...34 10 3 Model CHP205PX CHP255PX...
Page 38: ...36 10 4 Model CHP305PX...
Page 42: ...40...
Page 44: ...42...
Page 45: ...43 4 Parameter checking and setting Click Parameter then enter the password 0757...
Page 47: ...45...
Page 50: ......
Page 51: ...A0211MPX02...