INSTALLATION GENERAL
IMPORTANT NOTES
THE HEATRAVE S/L IS DESIGNED AND TESTED TO THE REQUIREMENTS OF BS5258 P16 AND IS
FITTED WITH AN ATMOSPHERE SENSING DEVICE
THE SUPER HEATRAVE CAN ONLY BE USED IN CONJUNCTION WITH THE FOLLOWING CHIMNEYS :
CONVENTIONAL BRICK OR STONE CHIMNEY. A PRE CAST FLUE CONFORMING TO BS 1289 PT.1 OR A
METAL FLUE BOX CONFORMING TO BS715, FURTHER DETAILS ARE COVERED LATER. A NON
COMBUSTABLE HEARTH MUST BE PROVIDED TO COMPLY WITH THE
BUILDING REGULATIONS OR A
SUITABLE PROPRIETARY FIRE SURROUND WITH A 100 DEGREES C RATING.
THE CHIMNEY OR FLUE (
UNLESS NEW
) MUST BE SWEPT BEFORE INSTALLATION IF IT HAS BEEN
USED FOR SOLID FUEL
*INSTALLER
THE APPLIANCE MUST BE INSTALLED BY A COMPETENT PERSON , IE A CORGI REGISTERED
INSTALLER IN ACCORDANCE WITH THE CURRENT EDITION OF THE GAS SAFETY (INSTALLATION
AND USE ) REGU;ATIONS OR THE RULES IN FORCE. FAILURE TO DO SO COULD LEAD TO
PROSECUTION
*REGULATIONS
THE FOLLOWING ARE THE RELEVANT CODES OF PRACTICE AND BRITISH STANDARDS:
BS5781 PART 2 1991, BS8303 1986, BS 5440 PART 1 1990 , BS1251 1987, BS 6891 1988 , BS 6461 PARTS 1 & 2
1984 , BS 715 1989 , BS 1289 PART 1 1986
THE BUILDING REGULATIONS ISSUED BY THE DEPARTMENT OF THE ENVIRONMENT
THE BUILDING STANDARDS (SCOTLAND) (CONSOLIDATION) REGULATIONS ISSUED BY THE
SCOTTISH DEVELOPMENT OFFICE
*VENTILATION
GREAT BRITAIN
NO SPECIAL VENTILATION BRICKS OR VENTS ARE NORMALLY REQUIRED INTO THE ROOM
CONTAINING THE APPLIANCE, PROVIDED NORMAL ADVENTITIOUS ROOM VENTILATION EXISTS.
THE INSTALLER MUST SATISFY THIS POINT BY CARRYING OUT A MANDATORY SPILLAGE TEST
IRELAND
PURPOSE PROVIDED VENTILATION MUST BE PROVIDED AND MUST HAVE A MINIMUM FREE AREA
OF 100 CM2
*WARNING
THIS APPLIANCE HAS A NAKED FLAME, AS WITH ALL SUCH FIRES IT IS RECOMMENDED THAT
A FIREGUARD SHOULD BE USED FOR THE PROTECTION OF CHILDREN, THE ELDERLEY AND
INFIRM. FIRE GUARDS SHOULD CONFORM TO BS 6539 (1984) ( FIREGUARDS FOR USE WITH SOLID
FUEL APPLIANCES)
ISSUE 1