34
TABLE 11.1c: CARLIN BURNER CONFIGURATION AND SETUP DATA
BOILER MODEL
FWZ081
FWZ100
FWZ130
FWZ160
BURNER MODEL
EZ1-LF
EZ1-LF
EZ1-LF
EZ-66
BLENDER
28 HOLE
NONE
NONE
NONE
CARLIN AIR TUBE NUMBER
50989
50989
50989
51198
STANDARD NOZZLE
DANFOSS
0.60 X 60AS
HAGO
0.75 X 60B
HAGO
1.00 X 45B
HAGO
1.35 X 45B
INSERTION LENGTH
2.62”
2.62”
2.62”
2.62”
PITCH ANGLE
1°
1°
1°
1°
PUMP PRESSURE (psi)
175
175
175
140
HEAD SETTING
2
2
3
5
STARTING AIR BAND SETTING
45%
35%
45%
60%
DRAFT IN FLUE (in w.c.)
0 to -0.02
0 to -0.02
0 to -0.02
0 to -0.02
MAX SMOKE
(Bacharach Scale)
#1
#1
#1
#1
FLUE CO
2
(%)
MIN.
MAX.
11.5
12.8
11.5
12.8
11.5
12.8
11.5
12.8