Product Manual — Doc. 7389C
GL-IPAC-SW8 • 42
Problem
Installation Resolution
Hardware
Resolution
Software Resolution
Timeclock
events are
not occurring.
N/A
N/A
Verify that timeclock
events are
programmed
properly.
Ensure that there are
no timeclock
overrides present.
Verify that the date
and time of the GL-
IPAC-SW8 are set
correctly.
Contact
closures do
not function.
Verify that the contact closure is being
triggered.
Verify that the
contact closure
wires are being
connected to the
contact closure
input and to the
ground terminal.
Verify that the
contact closure
is capable of
sinking 10 mA of
current and it
does not provide
current to the
input terminal.
Verify the contact
closure input is
programmed via the
Contact Closure
screen.
A city is not
available
from the
Project
Settings
screen.
N/A
N/A
Select a city that is
geographically close
and in the same time
zone as the current
city. The location
selection allows for
accurate calculation
of sunrise and sunset
times. Selecting a
nearby city may cause
the sunrise and sunset
times to be off by a
few minutes.