Weather-compensated boiler control is also possible (with outside sensor); in other words based
on the outside temperature. The controller has a programmed heating curve which determines the
water flow temperature together with the outside temperature. The heating curve must be chosen so
that the least favourable room can be efficiently heated even when the outside temperature is very
low.
See paragraph 5.5 for further information about weather-compensated control.
Clock program
The default clock program sets the temperature each day as follows:
• 06.00 – 19.00: 20°C
• 19.00 – 23.00: 21°C
• 23.00 – 06.00: 15°C +
T
You can of course adapt the clock programs to your own requirements.
See Chapter 5
.
5. Setting
5.1 Three usage modes
The controller has three usage modes:
•
Basic mode
: no clock programs are used in this mode. You can only set the temperature on the
controller manually.
•
Normal mode
: this is the standard mode. Most options are available, such as the clock
program.
•
Extended mode
: this mode lets you use two standard clock programs (A and B), change more
settings and request more detailed information.
You can change the usage mode via the menu:
Menu > Settings > Users > User mode
.