6.8.
The storage conditions
If the UPS is not in use and storage or storage is envisaged, the batteries must be recharged periodically
to avoid damaging them. Depending on the storage temperature, the power supply should be
connected at least every 6 months to charge the battery. Typically, the batteries are charged within 4
hours to 90% of their capacity, while it is recommended to leave the power supply on for a period of
24-48 hours to fully charge the batteries, which will extend their life.
Temp. storage up to 20 ° C
- charging every 6 months.
Temp. storage up to 3
0 ° C
- charging every 3 months.
Temp. storage up to 4
0 ° C
- charging every 1 month
6.9.
Battery change
If the operating time of the UPS is halved with the batteries working properly, or the UPS reports a
battery alarm, the batteries should be replaced immediately.
After disconnecting the batteries, the receivers are not protected against power outages.
It is not recommended to replace the batteries while the UPS and receivers are operating.
It is not allowed to replace the batteries while the UPS is operating in battery mode!