75
AGUAPLUS
COSMOGAS
Parameters
Ref.
Parameter description
Adjustment range
D e f a u l t
value
Individual
burner
(mod. 60
and 70)
Burner 1
(Master)
(mod. 100,
115 and
140)
Burner 2
(mod. 100,
115 and
140)
Customised
values
3001 Burner operation address
0 = Not in cascade
1 = Burner 1 (Master),
2 to 4 = Burner from 2 to 4 (slave
burners)
2
1
1
2
3002 Fan adjustment range
from 0 to 4
0
60 = 0
70 = 2
100 and 115 = 0
140 = 2
3003 Display unit of measurement
C = °C and bar;
F = °F and PSI;
C
C
C
C
3004 Water pressure switch
0 = Disabled; 1 = Enabled;
2 = N/A; 3 = N/A
1
1
1
0
3005
Burner flapper valve
0 = Disabled; 4 = Enabled;
8 = N/A; 12 = N/A
4
0
4
4
3006
Water flow rate sensor
0 = Disabled; 16 = N/A;
32 = N/A; 48 = Enabled
48
48
48
48
3007 Condensate level sensor
EnAb = Enabled;
dISA = Disabled
Enab
Enab
Enab
dISA
3008 Combustion gas sensor type
SEnS = Sensor; StCH = Switch
SEnS
SEnS
SEnS
SEnS
3009 External sensor type
10 = 10kohms; 12 = 12kohms;
10
10
10
10
3010 Other sensor type
10 = 10kohms; 12 = 12kohms;
10
10
10
10
3011
pump mode
0 = main c pump; 1 = N/A;
2 = N/A; 3 = N/A;
0
0
0
0
3012 domestic hot water operating mode
0 = only heating;
1= hot water storage tank;
2 = hot water tank with thermostat;
3 = N/A; 4 = N/A; 5 = N/A
0
0
0
0
3013 Reset Err 115
EnAb = Enabled;
dISA = Disabled
Enab
Enab
Enab
Enab
3015 Climatic adjustment: heating supply maximum
temperature (this parameter is overwritten by
parameter 3017)
from 20°C to 90°C
82°C
N/A
N/A
N/A
3016 Climatic adjustment: heating supply minimum
temperature
from 20°C to 90°C
20°C
N/A
N/A
N/A
3017 Supply maximum temperature (this parameter
takes priority with respect to parameter 3015)
from 20°C to 90°C
60°C
60°C
60°C
60°C
3018 Minimum supply temperature
from 20°C to 90°C
20°C
20°C
20°C
20°C
3020
Water flow rate sensor type
0 = N/A; 1 = DN8;
2 = DN 10; 3 = DN 15;
4 = DN 20; 5 = DN 25
4
4
4
4
3022 Minimum water pressure
from 0 to 5 bar
1
1
1
1
3035
Minimum water flow rate
from 0 to 100 l/min
45
60 = 40
70 = 45
100 e 115
= 40
140 = 45
100 e 115
= 40
140 = 45
3050 Slave burner number
from 0 to 3
3
0
1
3
3085 Modbus address
0 to 126
1
1
1
1
3086 Number of Stopbits
1 or 2
1
1
1
1
3100 Material selection
ABS; CPVC; PVC; SST; PP.
PVC
PVC
PVC
PVC
3101 Nation Selection
US, CA
US
US
US
US
Switch
“S4”
Switch “S4” position (see fig 15-11 and 15-12)
On or Off
On
On
On
Off
N/A = Not Applicable
17 - FORCED MENU
WARNING!!!
Editing these parameters could
cause the appliance and, therefore, the system to
malfunction. For this reason, only professionally
qualified technicians with in-depth knowledge and
awareness can edit them.
WARNING!!!
When accessing the forced
menu, it is possible for the appliance to start up;
ignoring this could cause damage to persons, animals
or objects.
WARNING!!!
In the event of the multi-burner
appliances (100 to 140 models), the display is always
connected to burner 1 (MASTER). To set the parameters
in the other burners, the display must be connected to
them as described in section 15.8.
The forced menu allows the appliance to be set based
on the system to serve. Setting occurs by adjusting the
available parameters (shown in the table).
To access the forced menu, proceed as follows:
1.- Power off the appliance by turning the main switch to the
OFF position;
2.- Holding down the RESET and
q
keys at the same
time, turn the main switch to the ON position;
3.- Wait for the word “INIT” or the
3000
parameters to
appear on the display.
4.- Using the
p
and
q
keys, scroll through the list of
3000
parameters;
5.- Navigate the menu using the
p
and
q
keys. Once
you have selected the parameter, press the RESET key
to make it editable via the
p
and
q
keys;
6.- Press the RESET key to save the changes;
7.- Wait 10 seconds;
8.- Power off the appliance;
9.- Repower the appliance to exit the forced menu and go
back to its normal operation.