13.5 - Conversion of appliance
models from 100 to 140 from
one type of gas to another
Appliances from 100 to 140 are multi-burners, which means
that the type of gas must be converted on every burner.
WARNING !!! Read these instructions carefully
before changing the gas:
- The gas equipment must be installed, calibrated or
modified by specialised personnel according to the
terms of the law;
- Check and be sure that the type of gas that is supplying
the appliance is compatible with the regulation kit you
have;
- Do not supply the appliance with a different type of gas
than those provided for.
Contents:
he Kit (supplied with the appliance) is composed of label
certifying the new type of gas, a gas nozzle for each burner
and an instruction sheet.
Carry out to change the gas, proceed as follows:
1.- Carry out the conversion in “Burner 1” (MASTER). See
Figure 13-5 to identify “Burner 1” (MASTER);
2.- Carry out the conversion in “Burner 1” (MASTER) following
points 1 to 16 of section 13.4;
After converting “Burner 1”, continue with “Burner 2” as shown
below:
3.- Carry out the conversion in “Burner 2” following points 1
to 16 of section 13.4;
After converting “Burner 2”, proceed as described below:
4 - Check the gas inlet pressure as described in section
13.7;
5 - Check the appliance power as described in section13.9;
WARNING !!!
The measurements taken
must be done with calibrated instruments that
guarantee an accurate reading.
6.- on the front casing of the appliance, in the place of the
label identifying the old adjustment status, apply the
self-adhesive plate
(see figure 13-7), bearing the new
adjustment status of the appliance, as follows: apply
label “B” if the appliance was converted from methane to
LP gas; apply label “A” if the appliance as converted from
LP gas to methane.
WARNING !!!
If there is a smell of gas:
A - Do not turn on any electrical device, including a
telephone, or any item that could cause sparks;
B - Immediately open doors and windows to create
a draught that will quickly clear the room of gas;
C - From another room, or failing that from a
neighbour’s, immediately call a qualified installer
or the gas supply company. In their absence, call
the fire departement.
13 - START-UP
D - Gas inlet pressure port
E - CO2 regulation screw
F - Factory regulation screw (do not touch)
Figure 13-6 - Gas valve
E
D
F
E
D
F