3  Series / Parallel operation 

in Modular power supply

3.1 Series operation

¡

Series operation is possible only between identical output mod-
ules.

  The copper bar for series connection is assembled before ship-

ping.

¡

The output current in series operation is the same as the one of 
the individual modules that are connected.

¡

Please note the following items,

 

1

Only same modules can be connected in series.

 

2

Total of the rated voltage in series has to be 48V or less.

    Adjusting output voltage is possible within 60V.
 

3

The series operation is not available along with the parallel op-

eration.

  Please contact us for any other conditions.

¡

When in series, the output voltage at the start-up might have the 
step as shown in Fig.3.1.

AC Input voltage

Input ON

Output voltage

Fig.3.1  Start-up waveform in series operation

4 Functions

4.1 Input voltage range

¡

The input voltage range is from 85 VAC to 264 VAC.

  The rated input voltage range for the safety approvals is from 

100VAC to 240VAC (50/60Hz).

¡

If the input voltage was out of the above range, the power supply 
might not meet the specification or might fail.

  Please do not apply the square wave of the UPS, the inverter and 

so on to the power supply.

4.2 Inrush current limiting

¡

If the switch is installed on the input, please select the one which 
can work at the inrush current.

¡

The relay is used in the inrush current limiting circuit. If the interval 
of the input on/off was short, the inrush current limiting might not 
work correctly.  So, please make its interval long enough.

  And, it makes the primary and the secondary inrush current.

4.3 Overcurrent protection

¡

The overcurrent protection which will activate at 105% or more of 
the rated current is built in.  The output will automatically recover 
when the overcurrent condition is resolved.

  Please do not use the unit with short circuit and/or under the over-

current condition.

¡

Hiccup mode

  When the overcurrent protection circuit activates and the output 

voltage drops, the output will get intermittent so that the average 
current decreases.

4.4 Thermal protection

¡

The unit has the thermal protection.

¡

The thermal protection circuit might activate and shut down the 
output under the following conditions.

 

1

 The case that the output current and/or the ambient tempera-
ture exceed the derating curve.

 

2

 The case that the fan stops working or the air volume is de-
creased by blocking the fan.

  When the thermal protection activates, outputs on all output mod-

ules will shut down.

  When either one of the following actions is taken, the output will 

recover.

 

1

 Turn the input voltage off and solve all of overheating cause.  
Then, turn the input on after enough time to cool the unit down.

 

2

 Turn all outputs off by GI terminal and solve all of overheating 
cause. Then, turn all outputs on by GI terminal after enough 
time to cool the unit down.

AC-DC Power Supplies Configurable Type

Instruction Manual

AME-11

Summary of Contents for AME1200F

Page 1: ...ility Material Single sided Double sided Series operation Parallel operation Input module of AME600F Active filter 67 Relay FR 4 Yes N A N A Half bridge converter 133 Input module of AME1200F Active f...

Page 2: ...protection AME 12 4 6 Output ripple and ripple noise AME 12 4 7 Output voltage adjustment AME 12 4 8 Remote ON OFF RC AME 12 4 9 Global inhibit GI AME 12 4 10 Isolation AME 13 4 11 Alarm AME 13 4 12...

Page 3: ...it ground 7 N C No connection 8 N C No connection 9 PR PR Alarm PRG 10 PRG PR Alarm ground Table 1 2 Pin configuration and function of CN2 Pin No Function Ground level 1 N C No connection 2 N C No con...

Page 4: ...LV Alarm LVG 4 LVG LV Alarm ground 5 N C No connection 6 N C No connection 7 N C No connection 8 N C No connection 9 N C No connection 10 N C No connection Do not connect anything to N C pins Table 1...

Page 5: ...V 2 5A Slot6 is blank AME1200F Order Name Construction 1 to 3 are same rules as Model Name after that add manage ment number 6 digits Parallel and series code are not listed on Order name Order Name e...

Page 6: ...rush current limiting circuit If the interval of the input on off was short the inrush current limiting might not work correctly So please make its interval long enough And it makes the primary and th...

Page 7: ...tion terminals Auxiliary power AUX for remote ON OFF The power supply has the auxiliary power AUX for the remote ON OFF The auxiliary power AUX is isolated from input output and FG Fig 4 3 is the exam...

Page 8: ...the isolation test between the input and the output the input and the FG and the output and the FG is conducted all outputs and terminals for all functions should be shorted 4 11 Alarm The unit has t...

Page 9: ...5 1 Installation method The unit has cooling fans Ensure that the inlet and outlet vents are not blocked Output module Air flow FAN Fig 5 1 Air flow Fig 5 2 is the recommended installation method whe...

Page 10: ...0 1300 Input voltage VAC Total output power W 1200 85 90 150 170 264 900 Fig 5 7 Derating curve for input voltage AME1200F Defintion of load factor Load maximum value in A0 to A6 A0 100 Sum of each mo...

Page 11: ...oltage Average ambient temperature yearly Warranty term 0 Io 75 75 Io 100 All mounting direction 85 to 170VAC Ta 40C or less 5 years 4 years Ta 50C 5 years 2 years 170 to 264VAC Ta 40C or less 5 years...

Reviews: