4.12 Auxiliary power (AUX)

¡

The unit has the auxiliary power (AUX: 5V1A) in CN1 to provide 
for the remote ON/OFF and external circuits.

¡

When the Global inhibit function activates, the following derating 
for the AUX is required.

    Derating for AUX: Io(AUX) 

[

 0.5A

¡

The AUX circuit(AUX, AUXG) is isolated from the input, the output, 
the FG, and other function terminals except GI1.

¡

If the output current of the AUX exceed 1A, the unit might be dam-
aged or malfunction.

  When the DC-DC converter is connected to the AUX, the cur-

rent might be severalfold of the normal current when starting up.  
Please check the current.

¡

The maximum external capacitor to the AUX is 47μF.

4.13 Medical Isolation grade

¡

AME series meets 2MOPP 

1MOPP

Safety GND

primary secondary

2MOPP

Fig.4.7  Medical Isolation Grade

5   Assembling  and   

Installation Method

5.1 Installation method

¡

The unit has cooling fans.

  Ensure that the inlet and outlet vents are not blocked.

Output

module

Air flow

FA

N

Fig.5.1 Air flow

¡

Fig.5.2 is the recommended installation method when the unit is 
mounted by screws. When the unit is installed by any other meth-
od, please take into account of its weight and secure it.

A

B

C

Top

Top

Top

CN1

CN1

CN1

Fig.5.2 Installation method 1

¡

Avoid installation method 2 as shown in Fig.5.3, which can cause 
stress on the mounting holes.

¡

Maximum length of mounting screws is 6mm (Refer to Fig.5.4).

NO

CN1

TOP

Chassis of

customer system

Screw M4

Chassis of 

AME series

6mm max

  

Fig.5.3 Installation method 2

Fig.5.4 Mounting screw

5.2 Output side attaching externally capacitor

¡

If the external capacitor is too large, the power supply might not 
start up.

Table 5.1  Connectable External capacitor on the output side [μF]

module code

capacitance

A

0 to 47,000

B

0 to 18,000

C

0 to 12,000

D

0 to 2,200

AC-DC Power Supplies Configurable Type

Instruction Manual

AME-14

Summary of Contents for AME1200F

Page 1: ...ility Material Single sided Double sided Series operation Parallel operation Input module of AME600F Active filter 67 Relay FR 4 Yes N A N A Half bridge converter 133 Input module of AME1200F Active f...

Page 2: ...protection AME 12 4 6 Output ripple and ripple noise AME 12 4 7 Output voltage adjustment AME 12 4 8 Remote ON OFF RC AME 12 4 9 Global inhibit GI AME 12 4 10 Isolation AME 13 4 11 Alarm AME 13 4 12...

Page 3: ...it ground 7 N C No connection 8 N C No connection 9 PR PR Alarm PRG 10 PRG PR Alarm ground Table 1 2 Pin configuration and function of CN2 Pin No Function Ground level 1 N C No connection 2 N C No con...

Page 4: ...LV Alarm LVG 4 LVG LV Alarm ground 5 N C No connection 6 N C No connection 7 N C No connection 8 N C No connection 9 N C No connection 10 N C No connection Do not connect anything to N C pins Table 1...

Page 5: ...V 2 5A Slot6 is blank AME1200F Order Name Construction 1 to 3 are same rules as Model Name after that add manage ment number 6 digits Parallel and series code are not listed on Order name Order Name e...

Page 6: ...rush current limiting circuit If the interval of the input on off was short the inrush current limiting might not work correctly So please make its interval long enough And it makes the primary and th...

Page 7: ...tion terminals Auxiliary power AUX for remote ON OFF The power supply has the auxiliary power AUX for the remote ON OFF The auxiliary power AUX is isolated from input output and FG Fig 4 3 is the exam...

Page 8: ...the isolation test between the input and the output the input and the FG and the output and the FG is conducted all outputs and terminals for all functions should be shorted 4 11 Alarm The unit has t...

Page 9: ...5 1 Installation method The unit has cooling fans Ensure that the inlet and outlet vents are not blocked Output module Air flow FAN Fig 5 1 Air flow Fig 5 2 is the recommended installation method whe...

Page 10: ...0 1300 Input voltage VAC Total output power W 1200 85 90 150 170 264 900 Fig 5 7 Derating curve for input voltage AME1200F Defintion of load factor Load maximum value in A0 to A6 A0 100 Sum of each mo...

Page 11: ...oltage Average ambient temperature yearly Warranty term 0 Io 75 75 Io 100 All mounting direction 85 to 170VAC Ta 40C or less 5 years 4 years Ta 50C 5 years 2 years 170 to 264VAC Ta 40C or less 5 years...

Reviews: