4.5 Overvoltage protection

¡

When the overvoltage protection activates, outputs on all output 
modules will shut down.

  When either one of the following actions is taken, the output will 

recover.

 

1

 Turn the input voltage off and solve all of overvoltage cause.  
Then, turn the input on after ten seconds.

 

2

 Turn all outputs off by GI terminal and solve all of overvoltage 
cause. 

    Then, turn all outputs on by GI terminal after ten seconds.

 *

 The recovery time varies depending on such factors as input 
voltage.

¡

If the external voltage was applied to the output of the power sup-
ply, the internal components might be damaged.

4.6 Output ripple and ripple noise

¡

The measurement environment would affect the output noise.

  Fig.4.1 is the recommended measurement method.

+Vout

-Vout

Load

150mm

C

1

Osiloscope/

Ripple noise meter

Bw:20MHz

Differential probe

+

C

1 : 

Aluminum electrolytic capacitor 22μF

Fig.4.1  Measuring method of Ripple and Ripple Noise

Remarks :

 

The output ripple and noise might not be measured correctly by 
the flux of magnetic force from the power supply which crosses 
the ground wire of the probe.

Bad example

Good example

Fig.4.2  Example of measuring output ripple and noise

4.7 Output voltage adjustment

¡

To increase the output voltage, turn the built-in potentiometer 
clockwise.

  To decrease the output voltage, turn it counterclockwise.

4.8 Remote ON/OFF(RC)

¡

Each output module have remote ON/OFF functions. The output 
voltage can be turned on/off by the signal to RC terminal in CN3 
on each modules.

¡

The remote ON/OFF circuit (RC, RCG) is isolated from the input, 
the output, FG and other function terminals.

¡

Auxiliary power (AUX) for remote ON/OFF.

  The power supply has the auxiliary power (AUX) for the remote 

ON/OFF.

  The auxiliary power (AUX) is isolated from input, output, and FG.
  Fig. 4.3 is the example of the remote ON/OFF with AUX.

¡

Please note the followings for the remote ON/OFF function.

 

1

 The output stops when 4.5V to 12.5V of  the voltage is applied 
to RC.

 

2

 The built-in fan does not stop even if the output is turned OFF 
by the remote ON/OFF.

 

3

 When the output is turned off by the remote on/off, the LV alarm 
will be delivered.

 

4

 This function individually operates on each output module.

¡

The Remote ON/OFF circuit on each output module can operate 
individually.

  The detail of the “Global inhibit function” to turn all output modules 

off at the same time is shown in the item 4.9.

CN3

CN1

RC

AUX

AUXG

RCG

SW

Output module

Output

on

Output

off

Ri=

1.8KΩ

Fig.4.3  Example of remote ON/OFF

Table 4.1  Remote ON/OFF specification

Connection method

Fig4.3 Remote SW

SW

Logic

Output on

SW open

(0-0.5V between RC and RCG)

Output off

SW short

(4.5-12V between RC and RCG)

Bases pin

CN3 RCG

4.9 Global inhibit (GI)

¡

The unit has the Global inhibit function.

  Global inhibit is the control signal input which turns all outputs off 

by supplying the current into GI2.

  Table 4.2 is specifications and Fig.4.4 is use examples for Global 

inhibit.

¡

The Global inhibit circuit (GI2, GIG) is isolated from input, output, 
FG, AUX and other function terminals.

¡

Please note the followings when using the Global inhibit function.

 

1

 The output can be turned off by supplying the current into GI2 
pin.

 

2

 The current into GI2 pin is 3mA typ (12mA max).

 

3

 The PR signal will get “High” when all output modules are 
turned off by the Global inhibit function.

AC-DC Power Supplies Configurable Type

Instruction Manual

AME-12

Summary of Contents for AME1200F

Page 1: ...ility Material Single sided Double sided Series operation Parallel operation Input module of AME600F Active filter 67 Relay FR 4 Yes N A N A Half bridge converter 133 Input module of AME1200F Active f...

Page 2: ...protection AME 12 4 6 Output ripple and ripple noise AME 12 4 7 Output voltage adjustment AME 12 4 8 Remote ON OFF RC AME 12 4 9 Global inhibit GI AME 12 4 10 Isolation AME 13 4 11 Alarm AME 13 4 12...

Page 3: ...it ground 7 N C No connection 8 N C No connection 9 PR PR Alarm PRG 10 PRG PR Alarm ground Table 1 2 Pin configuration and function of CN2 Pin No Function Ground level 1 N C No connection 2 N C No con...

Page 4: ...LV Alarm LVG 4 LVG LV Alarm ground 5 N C No connection 6 N C No connection 7 N C No connection 8 N C No connection 9 N C No connection 10 N C No connection Do not connect anything to N C pins Table 1...

Page 5: ...V 2 5A Slot6 is blank AME1200F Order Name Construction 1 to 3 are same rules as Model Name after that add manage ment number 6 digits Parallel and series code are not listed on Order name Order Name e...

Page 6: ...rush current limiting circuit If the interval of the input on off was short the inrush current limiting might not work correctly So please make its interval long enough And it makes the primary and th...

Page 7: ...tion terminals Auxiliary power AUX for remote ON OFF The power supply has the auxiliary power AUX for the remote ON OFF The auxiliary power AUX is isolated from input output and FG Fig 4 3 is the exam...

Page 8: ...the isolation test between the input and the output the input and the FG and the output and the FG is conducted all outputs and terminals for all functions should be shorted 4 11 Alarm The unit has t...

Page 9: ...5 1 Installation method The unit has cooling fans Ensure that the inlet and outlet vents are not blocked Output module Air flow FAN Fig 5 1 Air flow Fig 5 2 is the recommended installation method whe...

Page 10: ...0 1300 Input voltage VAC Total output power W 1200 85 90 150 170 264 900 Fig 5 7 Derating curve for input voltage AME1200F Defintion of load factor Load maximum value in A0 to A6 A0 100 Sum of each mo...

Page 11: ...oltage Average ambient temperature yearly Warranty term 0 Io 75 75 Io 100 All mounting direction 85 to 170VAC Ta 40C or less 5 years 4 years Ta 50C 5 years 2 years 170 to 264VAC Ta 40C or less 5 years...

Reviews: