2.3 Installation guidelines
2.4 Outdoor unit installation
When installing the outdoor unit, refer to "Precautions for
selecting the location
.
"
Check the strength and level of the installation ground so that
the unit will not cause any operating vibration or noise after
it
is
installed.
Fix the unit securely by means of the foundation bolts.
(Prepare 4 sets each of M8 or M10 foundation bolts,
nuts
,
and washers, which are available on the market.)
Whe
n
a wall or other obstacle is in the path of
the
outdoor unit
inlet or outlet airflow, follow the installation guidelines below.
For any of the below installation patterns, the wall height on the
outlet side should be 1200
mm
(
47.2
in
)
or less.
1) Installing
the
outdoor unit
2) Drain work
If drain work is necessary, follow the procedures below.
Use
a
drain plug for drainage.
If the drain port is covered by a mounting base or floor surface,
place additional foot bases of at least 1.2 in
(30 mm) in height
under the outdoor unit's feet.
In cold areas, do not use a drain hose with the outdoor unit.
(Otherwise, drain water may freeze, impairing heating
performance.)
Drain port
Bottom frame
Seal
Drain plug
Hose
Wall facing one side
Walls facing three sides
Walls facing two sides
1200
or less
Direction
of air
More than 100
More than 350
Side view
Top view
More than 50
More
than 100
More
than 350
More than 50
Top view
More than 50
More than 100
More than 350
8
Unit:
mm
Fix with bolts
(in
=
25.4
mm)