3.3   Installation of the throttle (

f

or some models)

Precautions

-

To

 ensur

e

 throttle efficiency, mount the throttle

 as

horizontally as possible.

-

Wrap the supplied anti-shock rubber 

on the outside 

of the

throttle 

to limit

 noise.

1      Anti-shock rubber
2      Throttle

Indoor

Indoor

Indoor

Outdoor

Outdoor

Outdoor

×

×

3.4   Purging air and checking gas leakage

    When piping work is completed, purge the

 

air and check for

    gas leakage.

WARNING

   Do not mix any substance other than the specified refrigerant 
   into the refrigeration cycle. 
   When refrigerant gas leaks, ventilate the room as soon as 

   

possible.

   The specified refrigerant should always be recovered and

 

 

   should

 

never be released directly into the environment.

   Use a vacuum pump for the specified refrigerant. Using the    

  

   

same vacuum pump for different refrigerants may damage

  

   t

he vacuum pump or the unit.

   If using additional refrigerant, perform air purging from the

 

   

 

   

refrigerant pipes and

 the

 indoor unit using a vacuum pump, th

e

n    

   

charge 

the 

additional refrigerant.

   Use a hexagonal wrench

 

(4

 

mm/0.2

 

in) to operate the stop

  

valve rod.

   All refrigerant pipe joints should be tightened with a torque    

   

  

wrench at the specified tightening torque.

1) Connect 

the 

projection side of 

the 

charging hose (which comes from

the 

gauge manifold) to 

the 

gas stop valve's service port.

2)

3)

4)

Full

y

 open 

the 

gauge manifold's low-pressure valve (Lo) and

completely close its high-pressure valve (Hi)

.

(The h

igh-pressure valve requires no operation.)

Perform

 vacuum pumping and make sure that the compound

pressure gauge reads -0.1

 

MPa (-76

 

cmHg).*1

Close 

the 

gauge manifold's low-pressure valve (Lo) and s

t

op

the 

vacuum pump.

(

Maintain

 this state for a few minutes to make sure the

compound pressure gauge pointer does not swing back.)*2

5)

Remove 

the 

caps from 

the l

iquid and gas stop valve

s

.

6)

Turn the liquid stop valve's rod 90 degrees counterclockwise

  

w

ith a hexagonal wrench to open 

the 

valve.

 

Close it after 5

seconds and check for gas leakage.

 

Using soapy water, 

check for gas leakage from 

the 

indoor unit's

 

flare and 

the 

outdoor unit's flare and valve rods.

 

After the check is 

complete, wipe

 off

all soapy water.

7)

Disconnect 

the 

charging hose from 

the 

gas stop valve's

service port

then fully open 

the 

liquid and gas stop 

valves. (Do not attempt to turn 

the 

valve rod b

e

yond its 

stop.)

8)

Tighten 

the 

valve and

 

service port caps for the liquid and

 

gas

stop valves with a torque wrench at the specified torques.

*1. Pipe length vs. Vacuum pump run time

10

1       Throttle 
2       Liquid pipe
3       Gas pipe

500m

m/19.

7in

1

2

3

Summary of Contents for SOPHIA CH-09MSPHCT-230VI

Page 1: ...nditioning unit Make sure to save this manual for future reference This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoo...

Page 2: ...n oxygen deficiency Use the attached accessories parts and specified parts for installation Otherwise the set may fall or water leakage electrical shock or fire may result Install the unit in a strong...

Page 3: ...ate the noise The appliance is not intended for use by young children or infirm persons without supervision Do not install the air conditioner in the following circumstances or locations The appliance...

Page 4: ...rect The unit may malfunction or components may burn out Is the unit safely grounded Dangerous at electric leakage Is the wiring size according to specifications The unit may malfunction or components...

Page 5: ...e properly drained The false ceiling is not on a noticeable incline There is sufficient clearance for maintenance and service There is no risk of flammable gas leaking The atmosphere is not potentiall...

Page 6: ...installation contact your dealer NOTE 5 Installation is possible with a ceiling dimension of 600 mm 23 6 in marked with However to achieve a ceiling panel overlapping dimension of 15 mm 0 6 in the spa...

Page 7: ...ing Consult the builder for details The center of the ceiling opening is indicated on the paper pattern for installation After removing the packaging material from the paper patten for installation at...

Page 8: ...adio wave conditions 8 In coastal areas or other places with a salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not...

Page 9: ...the wall height on the outlet side should be 1200 mm 47 2 in or less 1 Installing the outdoor unit 2 Drain work If drain work is necessary follow the procedures below Use a drain plug for drainage If...

Page 10: ...0 2 0 Flare dimension A mm Flare shape O 6 35 1 4 in O 6 35 1 4 in 15 16 N m 153 163 kgf cm 8 3 8 7 0 327 0 343 in 12 0 12 4 0 472 0 488 in 15 4 15 8 0 606 0 622 in 18 6 19 0 0 732 0 748 in 25 26 N m...

Page 11: ...ghtening torque 1 Connect the projection side of the charging hose which comes from the gauge manifold to the gas stop valve s service port 2 3 4 Fully open the gauge manifold s low pressure valve Lo...

Page 12: ...utdoor unit is factory charged with refrigerant Calculate the added refrigerant necessary according to the diameter and length of the liquid pipe of the outdoor indoor unit connection 3 6 Refrigerant...

Page 13: ...ain socket does not have to withstand unnecessary force To ensure a downward slope of 1 100 install hanging bars every 1 m 3 3 ft to 1 5 m 4 9 ft When unifying multiple drain pipes install the pipes a...

Page 14: ...ration will restart automatically if the main power supply is turned off and then turned back on again Be sure to ground the air conditioner Do not connect the ground wire to gas pipes water pipes lig...

Page 15: ...r supply terminal Looseness in the connection may cause overheating When connecting wires of the same gauge connect them according to the following figure 1 When attaching the control box lid make sur...

Page 16: ...Grille hook Open the intake grille and remove 1 Decoration panel 2 Screws M5 supplied with the panel After installing the decoration panel ensure that there is no space between the unit body and the...

Page 17: ...utton Check the following points If there is any malfunction please resolve it according to the Troubleshooting chapter in the user s manual The indoor unit The switch on the remote control works well...

Page 18: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details...

Reviews: