background image

4      CONNECT

ING

 THE DRAIN PIPE

4.1   Installation of drain piping

Install the drain piping as shown in 

the 

figure below and take 

measures against condensation. Improperly rigged piping could lead 
to leaks and

,

 eventually

,

 wet furniture and belongings.

-

Keep 

the 

piping as short as possible and slope it downward at

a

 

gradient of at least 1/100 so that air 

can

not 

stay

 trapped

inside the pipe.

-

Keep

 the

 pipe size equal to or greater than that of the

connecting

 

pipe (PVC pipe, nominal diameter 20

 

mm/0.8

 

in,

outside

 

diameter 25

 

mm/1

 

in).

-

Push the drain hose as far as possible over the drain socket

and tighten the metal clamp securely.

- Connect the drain hose to the drain raising pipes and

 

insulate

them.

- Connect the drain hose to the drain outlet on the indoor unit

and tighten it with the clamp.

4.3   How to perform piping

Precautions

Install the drain raising pipes at a height of less than 530 mm

(

20.9 in

)

.

Install the drain raising pipes at a right angle to the indoor
unit and no more than 300 mm

 (

11.8 in

)

 from the unit.

To prevent air bubbles, install the drain hose level

ly

 or slightly

tilted up (<

 

7

                         

                         

5 mm/3 in).

The incline of 

the 

drain hose should be 75 mm

 (

3 in

)

 or less so

the drain socket does not have to withstand 

unnecessary

 force.

To ensure a downward slope of 1:100, install hanging
bars every 1

 

m

 (

3.3

 

ft

)

 to 1.5 m

 (

4.9

 

ft

)

.

When unifying multiple drain pipes, install the pipes as
shown in 

the 

figure below. Select converging drain pipes whose

gauge is suitable for the operating capacity of the unit.

1         Ceiling slab
2         Hanger bracket
3         Adjustable range
4         Drain raising pipe
5         Drain hose 
6         Metal clamp 

1         T-joint converging drain pipes

12

1         Hanging bar
2         

1/100 gradient

1
2
3
4

         Drain socket (attached to the unit)

 

         

M

etal clamp 

         Drain hose
         Insulation (field supply)

- Insulate the drain hose inside the building.
- If the drain hose cannot be sufficiently set on a slope, fit the

 

hose with drain raising piping (field supply).

- Make sure that heat insulation work is executed on the

 

following 2 spots to prevent any possible water leakage due
to dew condensation

:

1   Indoor drain pipe
2   Drain socket 

1

2

3

4

0-530

100

1

1

1-1.5

 

m

1

2

×

4.2   Install the drain pipes

Drain piping connections
Do not connect the drain piping directly to sewage 
pipes that smell of ammonia. The ammonia in the 
sewage might enter the indoor unit through the drain 
pipes and corrode the heat exchanger. 

Keep in mind that 

water collecting on the drain pipe 

will block the drain pipe.

Unit: mm

Unit: mm

3

-

5

 

ft

1

2

0~75

5

1

-

1.5

 

m

300/11.8in

6 5

4

3

22

0/8.7in

750/29.5i

n

0~3

 

in

530/

20.

9i

n

3

-

5

 

ft

Summary of Contents for SOPHIA CH-09MSPHCT-230VI

Page 1: ...nditioning unit Make sure to save this manual for future reference This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoo...

Page 2: ...n oxygen deficiency Use the attached accessories parts and specified parts for installation Otherwise the set may fall or water leakage electrical shock or fire may result Install the unit in a strong...

Page 3: ...ate the noise The appliance is not intended for use by young children or infirm persons without supervision Do not install the air conditioner in the following circumstances or locations The appliance...

Page 4: ...rect The unit may malfunction or components may burn out Is the unit safely grounded Dangerous at electric leakage Is the wiring size according to specifications The unit may malfunction or components...

Page 5: ...e properly drained The false ceiling is not on a noticeable incline There is sufficient clearance for maintenance and service There is no risk of flammable gas leaking The atmosphere is not potentiall...

Page 6: ...installation contact your dealer NOTE 5 Installation is possible with a ceiling dimension of 600 mm 23 6 in marked with However to achieve a ceiling panel overlapping dimension of 15 mm 0 6 in the spa...

Page 7: ...ing Consult the builder for details The center of the ceiling opening is indicated on the paper pattern for installation After removing the packaging material from the paper patten for installation at...

Page 8: ...adio wave conditions 8 In coastal areas or other places with a salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not...

Page 9: ...the wall height on the outlet side should be 1200 mm 47 2 in or less 1 Installing the outdoor unit 2 Drain work If drain work is necessary follow the procedures below Use a drain plug for drainage If...

Page 10: ...0 2 0 Flare dimension A mm Flare shape O 6 35 1 4 in O 6 35 1 4 in 15 16 N m 153 163 kgf cm 8 3 8 7 0 327 0 343 in 12 0 12 4 0 472 0 488 in 15 4 15 8 0 606 0 622 in 18 6 19 0 0 732 0 748 in 25 26 N m...

Page 11: ...ghtening torque 1 Connect the projection side of the charging hose which comes from the gauge manifold to the gas stop valve s service port 2 3 4 Fully open the gauge manifold s low pressure valve Lo...

Page 12: ...utdoor unit is factory charged with refrigerant Calculate the added refrigerant necessary according to the diameter and length of the liquid pipe of the outdoor indoor unit connection 3 6 Refrigerant...

Page 13: ...ain socket does not have to withstand unnecessary force To ensure a downward slope of 1 100 install hanging bars every 1 m 3 3 ft to 1 5 m 4 9 ft When unifying multiple drain pipes install the pipes a...

Page 14: ...ration will restart automatically if the main power supply is turned off and then turned back on again Be sure to ground the air conditioner Do not connect the ground wire to gas pipes water pipes lig...

Page 15: ...r supply terminal Looseness in the connection may cause overheating When connecting wires of the same gauge connect them according to the following figure 1 When attaching the control box lid make sur...

Page 16: ...Grille hook Open the intake grille and remove 1 Decoration panel 2 Screws M5 supplied with the panel After installing the decoration panel ensure that there is no space between the unit body and the...

Page 17: ...utton Check the following points If there is any malfunction please resolve it according to the Troubleshooting chapter in the user s manual The indoor unit The switch on the remote control works well...

Page 18: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details...

Reviews: