background image

14

How to connect wiring 

Precautions

Remove the control box lid of the indoor unit.
Remove the cover of the outdoor unit. 

Follow the "Wiring diagram label" attached to the indoor unit's control box lid to wire the outdoor unit, indoor unit

,

 and remote control.

 

Securely fix the wires with a field

-

supplied c

l

amp. 

Attach the cover of the outdoor unit.

1         Control box lid
2         Wiring diagram label 
3         Power supply terminal block
4         Clamp for wiring
5         Wiring between units 
6         Plastic cover
7         Clamp (field supply)

Observe the notes mentioned below when wiring to the power 
supply terminal board.

Use the specified electric wire. Connect the wire securely to 
the terminal. Lock the wire down without applying excessive 
force to the terminal. (Tightening torque: 1.31

 

N.m

±

10%).

-

Do not connect wires of 

different gauge to the same

power

 

supply terminal. Looseness in the connection may

cause

 

overheating.

-

When connecting wires of the same gauge, connect them

according to the

 following

 figure

:

1

-

When attaching the control box lid, make sure not to pinch

any wires.

-

After all wiring connections are done, fill in any gaps in the

casing wiring holes with putty or insulation material (field
suppl

ied

) to prevent small animals or dirt from entering

 

the

unit and causing short circuits in the control

 

box.

Do not connect wires of 

different gauge to the same grounding 

terminal. Looseness in the connection may deteriorate the 
protection.

Use only specified wires and tightly connect 

them

 to the terminals.

 

Be careful that 

the 

wires do not place external stress on the 

terminals.

 

Keep 

them

 in neat order so that they do not obstruct other 

equipment

,

 such as 

by 

popping open the service cover. 

(

Make sure 

the cover closes tight

ly

.

)

 Incomplete connections could result in 

overheating and

,

 in the worst case, electric

al

 shock or fire. 

2

3

×

×

Cover

Bolts

1

2

4

5

6

3

7

Summary of Contents for SOPHIA CH-09MSPHCT-230VI

Page 1: ...nditioning unit Make sure to save this manual for future reference This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoo...

Page 2: ...n oxygen deficiency Use the attached accessories parts and specified parts for installation Otherwise the set may fall or water leakage electrical shock or fire may result Install the unit in a strong...

Page 3: ...ate the noise The appliance is not intended for use by young children or infirm persons without supervision Do not install the air conditioner in the following circumstances or locations The appliance...

Page 4: ...rect The unit may malfunction or components may burn out Is the unit safely grounded Dangerous at electric leakage Is the wiring size according to specifications The unit may malfunction or components...

Page 5: ...e properly drained The false ceiling is not on a noticeable incline There is sufficient clearance for maintenance and service There is no risk of flammable gas leaking The atmosphere is not potentiall...

Page 6: ...installation contact your dealer NOTE 5 Installation is possible with a ceiling dimension of 600 mm 23 6 in marked with However to achieve a ceiling panel overlapping dimension of 15 mm 0 6 in the spa...

Page 7: ...ing Consult the builder for details The center of the ceiling opening is indicated on the paper pattern for installation After removing the packaging material from the paper patten for installation at...

Page 8: ...adio wave conditions 8 In coastal areas or other places with a salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not...

Page 9: ...the wall height on the outlet side should be 1200 mm 47 2 in or less 1 Installing the outdoor unit 2 Drain work If drain work is necessary follow the procedures below Use a drain plug for drainage If...

Page 10: ...0 2 0 Flare dimension A mm Flare shape O 6 35 1 4 in O 6 35 1 4 in 15 16 N m 153 163 kgf cm 8 3 8 7 0 327 0 343 in 12 0 12 4 0 472 0 488 in 15 4 15 8 0 606 0 622 in 18 6 19 0 0 732 0 748 in 25 26 N m...

Page 11: ...ghtening torque 1 Connect the projection side of the charging hose which comes from the gauge manifold to the gas stop valve s service port 2 3 4 Fully open the gauge manifold s low pressure valve Lo...

Page 12: ...utdoor unit is factory charged with refrigerant Calculate the added refrigerant necessary according to the diameter and length of the liquid pipe of the outdoor indoor unit connection 3 6 Refrigerant...

Page 13: ...ain socket does not have to withstand unnecessary force To ensure a downward slope of 1 100 install hanging bars every 1 m 3 3 ft to 1 5 m 4 9 ft When unifying multiple drain pipes install the pipes a...

Page 14: ...ration will restart automatically if the main power supply is turned off and then turned back on again Be sure to ground the air conditioner Do not connect the ground wire to gas pipes water pipes lig...

Page 15: ...r supply terminal Looseness in the connection may cause overheating When connecting wires of the same gauge connect them according to the following figure 1 When attaching the control box lid make sur...

Page 16: ...Grille hook Open the intake grille and remove 1 Decoration panel 2 Screws M5 supplied with the panel After installing the decoration panel ensure that there is no space between the unit body and the...

Page 17: ...utton Check the following points If there is any malfunction please resolve it according to the Troubleshooting chapter in the user s manual The indoor unit The switch on the remote control works well...

Page 18: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details...

Reviews: