25
COOLIUS Y50A
4.11 Vessel charge
The equipment may not contain enough refrigerant to run. The available quantity could be negative
(Es: -500 g.) It will be necessary to add new refrigerant into the internal vessel before the use (at least 3 or 4
Kg).
1. Turn
COOLIUS SELECT
to select
Vessel charge
. Press
ENTER
to confirm.
NOTE:
The message is shown before processes.
2.
Connect the LP (BLUE) or the HP (RED) hose to a new
tank of refrigerant. If available, open the liquid tank valve
(RED).
Otherwise turn the tank up-side-down.
3. Turn
COOLIUS SELECT
to set the value.
• Minimum: 800 g.
• Maximum: the value shown by the display.
4. Press
ENTER
to confirm..
5. Press
START
key to confirm
MESSAGE:
If the equipment senses a pressure
lower than the minimum value for the process.
The process starts.
WARNING!
Verify Oil/UV
quantity in the
bottles.
Connect LP or HP
hose to ext. tank.
Open the valve
liquid side.
Set the quantity.
g./////
Confirm by “START”
Check:
Ext. tank empty or
tank valve closed.
Vessel charge in
process.
Pressure mb.
Refrigerant g./////