23
COOLIUS Y50A
4.10 Refrigerant Test
The machine has a built-in refrigerant analyzer SAE J2927 which is manufactured by NEUTRONICS Inc.
ATTENTION!
Maintenance and servicing of the Refrigerant Analyzer must be performed by authorized
personnel only!
NOTE:
The refrigerant test is automatically performed when the recovery of refrigerant is part of
the process selected (e.g.
FULL SERVICE
,
RECOVERY
,
Recovery / Vacuum
).
This avoids the use of non-compliant refrigerant fluid.
It is also possible to perform the Refrigerant Test on a refrigerant tank or on an A/C system as a single
process.
Connect the HP or LP hose to the refrigerant tank or to the A/C system that has to be tested.
1. Turn
COOLIUS SELECT
to select
Other selections
.
Press
ENTER
to confirm.
2. Turn
COOLIUS SELECT
to select
Refrigerant TEST
Press
ENTER
to confirm.
3. Press
START
key to confirm.
MESSAGE:
If the equipment senses a lower
pressure than the minimum value for the process.
Please check the pressure on HP/LP gauges.
Press
STOP
to end.
If the pressure is above the minimum pressure value
required to perform the test, then the process starts.
Refrigerant Test
Refrigerant Test
Confirm by “START“
Not enough pressure
for Refrigerant
Quality Test
Refrigerant Test
in process.
Please wait!