8. Menu 75 Parameters
ALSPA PROFIBUS Field Bus Coupler
Page 8-12
Technical Manual
(09/06)
Par No Description
Default Range
Attr.
Comment
75.33
Value 3 Source
0
0 - 99.99
E.S.N See page 8-6
75.34
Value 4 Source
0
0 - 99.99
E.S.N See page 8-6
75.35
Value 5 Source
0
0 - 99.99
E.S.N See page 8-6
75.36
Raw data 1
0
±
32767
75.37
Raw data 2
4
0
±
32767
5
75.38
Raw data 3
4
0
±
32767
5
75.39
Raw data 4
4
0
±
32767
5
75.40
Raw data 5
4
0
±
32767
5
75.41
Raw data 6
4
0
±
32767
5
75.42
Rx Error Word
R
75.43
Rx Error Count
R
75.44
Tx Error Word
R
75.45
Tx Error Count
R
75.46
Fbus Comms. state
0 - 3
R
Where for Attributes :
N
-
ENTER has to be pressed to update
O
- Operator
Accessible
E
- Engineer
Accessible
L
- List
Parameter
S
-
Stop Drive To Edit
R
- Read
Only
7
For software Version 8.00 or earlier P75.36 to P75.41 are visible.
For software Version 9.00 or later P75.36 to P75.41 are not available, the SPY facility
should be used as follows:
Received data- Set P89.00=75.00 and view received data in P8900 onwards.
Transmitted data-Set P89.00=75.30 and view data for transmission in P89.01
onwards.
8
Raw data may be received having a value of –32768. This will display as “uncollated”
on the keypad but will nevertheless be transferred correctly.