Table 8-7 Menu 75
Par No Description
Default Range
Attr.
Comment
75.00
Expansion bus device
Set by
hard-
ware
3 = Fieldbus Coupler
R
See page 8-2
75.01
Protocol ID
0
Reserved for future use
R
Not used
75.02 Node
Address
255
0 to 127 (4002: 0 to 255)
E
See page 8-2
75.03
Protocol
3
4002= 2 or 3
4001 FIXED= 3
E.L
See page 8-2
75.04 Automatic
configuration
at power up
0
0= Prevent, 1 = Allow
E.L
75.05
Configure Link
0
1 to configure. Automatically
reset to 0 by a configuration
attempt.
E.L See
75.06
Action on loss of
PROFIBUS control
source.
1
0 = Ignore
1 = Warning
2 = Trip
E.L See
75.07
Freeze / Fallback
1
0 = Freeze
1 = Fallback
E.S.L
75.08
Control Word 1
0
0 – FFFF
R
75.09
Control Fallback 1
0
0 – FFFF
E
75.10
Control Word 2
0
0 – FFFF
R
75.11
Control Fallback 2
0
0 – FFFF
E
75.12 Reference
1
0
±
100.00
75.13 Fallback
1
0
±
100.00
75.14 Reference
2
0
±
100.00
75.15 Fallback
2
0
±
100.00
75.16 Reference
3
0
±
100.00
75.17 Fallback
3
0
±
100.00
75.18 Reference
4
0
±
100.00
75.19 Fallback
4
0
±
100.00
75.20 Reference
5
0
±
100.00
75.21 Fallback
5
0
±
100.00
75.22
CW 1 Pointer
0
0 - 99.99
E.S.N See page 8-5
75.23
Ref. 1 Pointer
0
0 - 99.99
E.S.N See page 8-5
75.24
Ref. 2 Pointer
0
0 - 99.99
E.S.N See page 8-5
75.25
Ref. 3 Pointer
0
0 - 99.99
E.S.N See page 8-5
75.26
Ref. 4 Pointer
0
0 - 99.99
E.S.N See page 8-5
75.27
CW 2/Ref. 5 Pointer
0
0 - 99.99
E.S.N See page 8-5
75.28
Value for 100% Ref.
10000
0
±
32767
75.29
Scale Reference Mask
001Eh
0-FFFFh
E.S
75.30
Status word Source
0
0 - 99.99
E.S.N See page 8-6
75.31
Value 1 Source
0
0 - 99.99
E.S.N See page 8-6
75.32
Value 2 Source
0
0 - 99.99
E.S.N See page 8-6
6
This parameter requires a PROFIBUS reconfiguration before changes can take
effect.