ARCHITECTURAL AND ENGINEERING SPECIFICATION, v 2.7
43
1. The system shall allow for ‘Activity Links’ that provide the capability to control
relays based on an event.
2. Shall allow the CA3000 to be a direct replacement for the Sensormatic AC500
system.
3. Shall allow triggering of activity link in case any of the following events occur:
a. AC Power Fail/Restore
b. Input Abnormal/Normal
c. Input Supervisory Open/Short/Fault
d. Relay On/Off
e. Link Activate/Deactivate
f. Forced Door
g. Door Closed
h. Door Bypass
i. Door Free Access Start/End
j. Door Open Too Long
k. Door Key Code Entry
l. Manual Door Unlock/Lock
m. Manual Door Enable/Disable
n. Low/High Watermark
o. Valid Badge
p. Valid Badge Enabled
q. Valid Badge Disabled
r. Duress Access
s. Denied Void Badge
t. Denied Facility Match
u. Denied Time Of Day
v. Denied Issue Level
w. Denied Unauthorized
x. Denied PIN Violation
y. Denied APB IN/OUT
z. Denied Escort Match
aa. Denied Reissue
bb. Denied Vehicle Tag Match
cc. Violate Exit Override
dd. Violate Entry Override
ee. Violate Time Of Day Override
ff. Denied Interactivity Timeout
gg. Activity Link ON/OFF
4.
Category Counters:
The Activity Link operation shall also include 16 category
counters which allow the cardholder to trip a single or multiple activity links.
5.
Watermarks:
The watermark feature shall allow the system to ‘count’ the amount
of cardholders/vehicles in a particular area. The user shall have the ability to set
‘high’ and ‘low’ marks for the system to increment and decrement the
card/vehicle count. This can be used to disable a reader and disallow any further
activity into the area until the watermark drops below the preset mark.