47
maximum temperature for operation (temperature label on the back of the device -
Installation
of the device
).
If it is found that there have been changes in the volume or type of risk in the protected area, a
new fire protection solution must be developed to provide the original level of protection. It is
recommended to regularly check the level of the fire extinguisher using the
Status
web
interface. At the same time, the weekly control procedure is carried out.
Extinguisher concentration level is indicated by a blue line on the right side of the screen if
reached OR a red line if not reached
Figure Number 39 - Status panel with fire extinguisher level indicator (full)
○
Service provider inspection
■
Annual service inspection
The inspection is carried out by a person trained by the manufacturer/distributor. This is a
functional check of the entire system, looking mainly at the detection, pressure and discharge
parts of the device. A visual and physical inspection will be carried out incl. functionality of
the mentioned circuits. At the same time, a weekly and monthly inspection is carried out.
■
2-year service inspection
The inspection is carried out by a person trained by the manufacturer/distributor. Emphasis is
placed on the correct functionality of the entire device. The quality of the contained fire
extinguisher, the condition of the pressure parts of the device, and the functionality of the
battery are assessed. At the same time, a weekly, monthly and annual inspection was carried
out. If this service check is not carried out by the manufacturer/distributor, the manufacturer
bears no legal responsibility for the malfunctioning of the device.
○
List of repairs and inspections performed by service provider
▪
Repairs may only be carried out by properly trained personnel of a service organization
with qualifications in the field of electricity in accordance with the relevant regulations.