34
Figure number 33 - Upload
Backup: saving the device configuration for backup.
Restore: restoring the device from the backup file.
Reset: resetting the device.
Choose file…: import the language settings file.
Save: saving language settings.
○
MODBUS RTU
RS485 parameters:
Baud rate – 2400, 4800, 9600, 19200
Lenght – 8 bits
Stop Bit – 1
Parity – None
ModBus parameters:
ID – defined by user
Fucntion codes – 1, 4, 5
Function 4 - read coils
Table number 4.
Alarm
Reg State - 0
State - 1
Reg Error - 1
Zone 1
0
OK
Extinguishing
50
Failure
Zone 2
1
OK
Extinguishing
51
Failure
Zone 3
2
OK
Extinguishing
52
Failure
Fire sensor1
3
OK
Fire
53
Failure
Fire sensor2
4
OK
Fire
54
Failure
External button
9
Off
On
59
Failure
Door
10
Closed
Open
60
Failure
Propellant gas
pressure
11
OK
Low
61
External Sounder
12
Sound activated
62
Failure