TDMA CONTROL 602-702 Eng Nov.doc
26
Example of CONTROL 602:
Room sensor active
Yes
Heating off at
1 K above room set temperature
Room temperature required:
20°C
When the room reaches 21
O
C the controller will shut of the boiler, boiler
pump and heating circuit pump and closes the mixing valve.
For the CONTROL 702: With more than one TR-CONTROL Touch, the
boiler and boiler pump are only turned off when all the “heating off”
temperatures have been reached.
The heating is switched back on when the room reaches 20.5
O
C.
Temperature rising at:
0 … 40 °C
Here you set the room temperature, which is required on activation of
“temperature raising”.
Temperature raising for:
0,5 … 12 h
Here you can set the time period for the how long you want the room
temperature to increase.
Temperature lowering to:
0 … 40 °C
Here you can set the reduction in room temperature required.
Temperature lowering for:
0,5 … 12 h
Here you can set the time period for how long you want the room temperature
to decrease.
Ventilate room temperature target:
0… 30 °C
Here you can set the minimum room temperature at which the heating system
must switch on again.
Wall Correction:
-‐ 10 + 10°C
Here you can correct the room temperature measurement.