TDMA CONTROL 602-702 Eng Nov.doc
54
6
Asembly CONTROL 602
The unit must be restricted to indoor use only.
Authorised personnel must carry out all work under the relevant local and
national guidelines.
Note to VDE Guidelines
The relevant local and IEE regulations must be observed. The sensor cables
carry low voltage and should not share a trunking with cables carrying more
than 50 V.
Note on Electrical Wiring
The pin assignments of inputs and outputs occur under the controller
connection information in Section 5.13 and 5.14.
Note on the Position of the Collector Sensor
The sensor should be mounted on the last possible absorber plate
(TUBO 12), so as to be able to pick up the maximum insolation.
If a pocket is used (PLANO 27), a good contact must be made
between the sensor and the pocket. The use of heat conducting
paste is recommended. In no case should the sensor be mounted
outside of the collector.
Incorrect positioning of the sensor can lead to inaccurate
collector temperature measurement and thus the controller will
not function correctly.
6.1
Mounting the CONTROL 602
Caution
The controller should only be opened after the power has been disconnected
from it. Risk of electrical stock and death!
Note for Mounting the Controller
The template, included, should be used to mount the controller.
After removing the screw (1) the front cover can be tilted up from the front (2)
and removed (see picture opposite). When you reinsert the upper part make
sure the hinges slide into the slots provided, before lowering the front section
and refixing the screw.
2
1