ADMINISTRATION PARAMETERS
------------ ALARM VALIDATION -----------
ALARM MANAGEMENT STANDARD S10-20 NO
- ALARM BEGIN. IF OPEN LOOP NO
RECORD PARKED EXTENSIONS IN LOGBOOK YES
LOGBOOK OUTPUT ON PRINTER NO
----------------------------------------
Figure 60: Administration parameters (continued - alarm validation on F1)
ADMINISTRATION PARAMETERS
------------ ALARM VALIDATION ---------
RECTIFIER ALARM NO
OCCURRENCE FREQUENCY NO
MAINS OR BATTERY ALARM NO
FAN UNIT ALARM NO
OCCURRENCE FREQUENCY YES
alarm management STANDARD S10-20
- ALARM BEGIN. IF OPEN LOOP NO
RECORD PARKED EXTENSIONS IN LOGBOOK YES
LOGBOOK OUTPUT ON PRINTER NO
----------------------------------------
Figure 61: Administration parameters (continued - alarm validation on F2)
RECTIFIER ALARM (F2)
NO YES
If you enter YES, logbook and printer output: the mains is connected but there is a rectifier
malfunction.
OCCURRENCE FREQUENCY (F2)
Alarm output frequency: minimum 30 minutes, maximum 240 minutes.
MAINS OR BATTERY ALARM (F2)
NO YES
If you enter YES, logbook and printer output: this indicates a switch from MAINS to
BATTERY power.
FAN UNIT ALARM (F2)
NO
YES
If you enter YES, logbook and printer output: this indicates that the fans are stopped.