Nortec SAM-e Installation
Pressurized Plumbing without External Separator
Note: The Nortec SAM-e header functions as a steam separator, therefore an external
steam separator is not required.
• Steam components in grey provided by Condair.
• Tap steam from top of pressurize steam main to avoid excess condensate.
• Condensate from
Nortec
SAM-e to be returned to atmospheric floor drain.
When pressurized steam enters Nortec SAM-e, pressure drops down to almost atmospheric
pressure. Therefore, it must be drained atmospherically, and the use of a condensate pump (rated
for 212ºF) must be used to raise condensate to a higher elevation.
1” Air Gap
Drain
Strainer
Manual Shut-Off
Valve (By Others)
Pressurized
Steam Main
6” min.
Return to non-pressurized
floor drain
Pressurized condensate
return main
Tap steam from top of
pressurized steam main
Summary of Contents for Nortec Mini SAM-e
Page 1: ...DELETE THIS PAGE AFTER PRINTING OR GENERATING PDF...
Page 7: ...3 Nortec SAM e Installation Identify your Components...
Page 8: ...Nortec SAM e Installation 4 Identify your Optional Components...
Page 11: ...7 Installation Nortec SAM e In Duct...
Page 19: ...15 Nortec SAM e Installation Installation in Vertical Duct...
Page 21: ...17 Nortec SAM e Installation Nortec Mini SAM e Installation Procedures...
Page 22: ...Nortec SAM e Installation 18 Nortec Mini SAM e Assembly General Installation...
Page 25: ...21 Nortec SAM e Installation Plumbing...
Page 28: ...Nortec SAM e Installation 24 Internal Baffle Plate...
Page 36: ...Nortec SAM e Installation 32...
Page 37: ...33 Nortec SAM e Installation Atmospheric Steam Lines...
Page 48: ...Nortec SAM e Installation 44 Figure 8 Long Steam Run...
Page 49: ...45 Nortec SAM e Installation Atmospheric Steam Lines...
Page 57: ...53 Nortec SAM e Installation 3 Fit shields to tubes 4 Secure with stainless straps...
Page 58: ...Nortec SAM e Installation 54 5 Completed tube...
Page 59: ...55 Nortec SAM e Installation Troubleshooting Maintenance Spare Parts...