Nortec SAM-e Installation |
56
Troubleshooting
Steam tubes discharge water:
1 Steam supply pipe is not insulated.
2 Steam supply pipe not properly drained or sloped.
3 Manifold or adapter condensate drain is clogged or malfunctioning.
4 Excessive back-pressure in condensate drain pipe (due to pressure in secondary condensate
drain); must be piped to non-pressurized condensate return.
5 Primary and secondary condensate drains are both joined together.
6 Condensate line has been routed too high (causing static back pressure).
Maintenance
Inspect Nortec SAM-e at start-up.
1 For humidifier maintenance schedule, refer to Installation, Operation, and Maintenance
Manual for your humidifier.
Spare Parts
Kit Part #
Kit description
Quantity in Kit
1503812
SAM-e coupling seal for steam tubes (1 per tube)
1
2546662
Insertion stop (1 per tube) (Galvanized)
10
2578156
Insertion stop (1 per tube) (Stainless Steel)
10
2546665
5/16” Locknuts, bolts, washers (Galvanized)
10
2546668
5/16” Locknuts, bolts, washers (Stainless Steel)
10
2546667
1/4" bolts, washers (1 per tube) (Galvanized)
10
2578157
1/4" bolts, washers (1 per tube) (Stainless Steel)
10
2538346
SAM-e insulated tube strapping
1
2538347
SAM-e insulated header strapping
1
2538344
SAM-e insulated dual-inlet header strap (for second inlet)
1
Summary of Contents for Nortec Mini SAM-e
Page 1: ...DELETE THIS PAGE AFTER PRINTING OR GENERATING PDF...
Page 7: ...3 Nortec SAM e Installation Identify your Components...
Page 8: ...Nortec SAM e Installation 4 Identify your Optional Components...
Page 11: ...7 Installation Nortec SAM e In Duct...
Page 19: ...15 Nortec SAM e Installation Installation in Vertical Duct...
Page 21: ...17 Nortec SAM e Installation Nortec Mini SAM e Installation Procedures...
Page 22: ...Nortec SAM e Installation 18 Nortec Mini SAM e Assembly General Installation...
Page 25: ...21 Nortec SAM e Installation Plumbing...
Page 28: ...Nortec SAM e Installation 24 Internal Baffle Plate...
Page 36: ...Nortec SAM e Installation 32...
Page 37: ...33 Nortec SAM e Installation Atmospheric Steam Lines...
Page 48: ...Nortec SAM e Installation 44 Figure 8 Long Steam Run...
Page 49: ...45 Nortec SAM e Installation Atmospheric Steam Lines...
Page 57: ...53 Nortec SAM e Installation 3 Fit shields to tubes 4 Secure with stainless straps...
Page 58: ...Nortec SAM e Installation 54 5 Completed tube...
Page 59: ...55 Nortec SAM e Installation Troubleshooting Maintenance Spare Parts...