Nortec SAM-e Installation |
38
Nortec RS Steam-Line
Table 4: SE Steam-Line
Nortec
Humidifier
Steam
output
[ lb ]
MED-L copper
tube nominal
steam line size
Stainless steel
tube diameter
(wall thickness
0.065”)
Steam loss per
foot in
condensation
[ lb/ft ]
Steam line
maximum
equivalent
length
RS 010
10
1-1/2”
1-3/4”
0.11
12 ft
RS 015
15
1-1/2”
1-3/4”
0.11
15 ft
RS 020
20
1-1/2”
1-3/4”
0.11
18 ft
RS 030
30
1-1/2”
1-3/4”
0.11
27 ft
RS 045
45
1-1/2”
1-3/4”
0.11
43 ft
RS 065
65
1-1/2”
1-3/4”
0.11
47 ft
RS 090
90
1-1/2”
1-3/4”
0.11
48 ft
RS 135
135
2 x
1-1/2”
2 x
1-3/4”
0.11
47 ft
RS 180
180
2 x
1-1/2”
2 x
1-3/4”
0.11
48 ft
• Based on 3” duct static pressure.
• Maximum duct static pressure for resistive element units is 6”w.c.
Summary of Contents for Nortec Mini SAM-e
Page 1: ...DELETE THIS PAGE AFTER PRINTING OR GENERATING PDF...
Page 7: ...3 Nortec SAM e Installation Identify your Components...
Page 8: ...Nortec SAM e Installation 4 Identify your Optional Components...
Page 11: ...7 Installation Nortec SAM e In Duct...
Page 19: ...15 Nortec SAM e Installation Installation in Vertical Duct...
Page 21: ...17 Nortec SAM e Installation Nortec Mini SAM e Installation Procedures...
Page 22: ...Nortec SAM e Installation 18 Nortec Mini SAM e Assembly General Installation...
Page 25: ...21 Nortec SAM e Installation Plumbing...
Page 28: ...Nortec SAM e Installation 24 Internal Baffle Plate...
Page 36: ...Nortec SAM e Installation 32...
Page 37: ...33 Nortec SAM e Installation Atmospheric Steam Lines...
Page 48: ...Nortec SAM e Installation 44 Figure 8 Long Steam Run...
Page 49: ...45 Nortec SAM e Installation Atmospheric Steam Lines...
Page 57: ...53 Nortec SAM e Installation 3 Fit shields to tubes 4 Secure with stainless straps...
Page 58: ...Nortec SAM e Installation 54 5 Completed tube...
Page 59: ...55 Nortec SAM e Installation Troubleshooting Maintenance Spare Parts...