39 |
Nortec SAM-e Installation
Effective Length of Typical Steam-Line Fittings
Table 5: Effective length of Typical Steam-Line Fittings
Nominal tube
size
Standard
90°-elbow
Standard
45°-elbow
Side-outlet
tee
Gate valve*
Globe valve*
3/4”
2 ft
1 ft
4 ft
0.4 ft
18 ft
7/8”
2 ft
1 ft
4 ft
0.4 ft
18 ft
1-1/2”
3.5 ft
1.75 ft
7 ft
0.8 ft
34 ft
1- 3/4”
3.5 ft
1.75 ft
7 ft
0.8 ft
34 ft
3”
5 ft
2.5 ft
11 ft
1.1 ft
54 ft
4”
8 ft
4 ft
15 ft
1.6 ft
80 ft
*Valve in full open position.
Material for Steam Lines
Table 6: Effective length of Typical Steam-Line Fittings
Material
Type
Note
Copper
MED-L Tube
Recommended.
Stainless steel Tube wall thickness 0.065”
Recommended.
Required for RO/DI water.
Flex-hose
High-temperature rubber
hose
Condair high-temperature flex-hose recommended only.
Condair flex-hose to be checked every 5 years.
Other brands of steam hose may:
-
Carry odors
-
Kink or deform
-
Create back-pressure and affect humidifier
performance
Black pipe
Schedule 40
Schedule 40
Not recommended
Oil seeps out.
Rusting.
Health hazard.
Larger pressure drop.
Plastic
-----
Not recommended
Summary of Contents for Nortec Mini SAM-e
Page 1: ...DELETE THIS PAGE AFTER PRINTING OR GENERATING PDF...
Page 7: ...3 Nortec SAM e Installation Identify your Components...
Page 8: ...Nortec SAM e Installation 4 Identify your Optional Components...
Page 11: ...7 Installation Nortec SAM e In Duct...
Page 19: ...15 Nortec SAM e Installation Installation in Vertical Duct...
Page 21: ...17 Nortec SAM e Installation Nortec Mini SAM e Installation Procedures...
Page 22: ...Nortec SAM e Installation 18 Nortec Mini SAM e Assembly General Installation...
Page 25: ...21 Nortec SAM e Installation Plumbing...
Page 28: ...Nortec SAM e Installation 24 Internal Baffle Plate...
Page 36: ...Nortec SAM e Installation 32...
Page 37: ...33 Nortec SAM e Installation Atmospheric Steam Lines...
Page 48: ...Nortec SAM e Installation 44 Figure 8 Long Steam Run...
Page 49: ...45 Nortec SAM e Installation Atmospheric Steam Lines...
Page 57: ...53 Nortec SAM e Installation 3 Fit shields to tubes 4 Secure with stainless straps...
Page 58: ...Nortec SAM e Installation 54 5 Completed tube...