Nortec SAM-e Installation |
36
Nortec Gas Steam-Line
Table 2: Gas Steam-Line
Nortec
Humidifier
Steam
output
[ lb ]
MED-L copper
tube nominal
steam line size
Stainless steel
tube diameter
(wall thickness
0.065”)
Steam loss per
foot in
condensation
[ lb/ft ]
Steam line
maximum
equivalent
length
GS 100
100
1-1/2”
1-3/4”
0.11
90 ft
GS 200
200
3”
3”
0.16
90 ft
GS 300
300
3”
3”
0.16
180 ft
GS 400
400
4”
4”
0.22
180 ft
GS 500
500
4”
4”
0.22
220 ft
GS 600
600
4”
4”
0.22
260 ft
• Based on 3” duct static pressure.
• Maximum duct static pressure for GS is 12” w.c.
Summary of Contents for Nortec Mini SAM-e
Page 1: ...DELETE THIS PAGE AFTER PRINTING OR GENERATING PDF...
Page 7: ...3 Nortec SAM e Installation Identify your Components...
Page 8: ...Nortec SAM e Installation 4 Identify your Optional Components...
Page 11: ...7 Installation Nortec SAM e In Duct...
Page 19: ...15 Nortec SAM e Installation Installation in Vertical Duct...
Page 21: ...17 Nortec SAM e Installation Nortec Mini SAM e Installation Procedures...
Page 22: ...Nortec SAM e Installation 18 Nortec Mini SAM e Assembly General Installation...
Page 25: ...21 Nortec SAM e Installation Plumbing...
Page 28: ...Nortec SAM e Installation 24 Internal Baffle Plate...
Page 36: ...Nortec SAM e Installation 32...
Page 37: ...33 Nortec SAM e Installation Atmospheric Steam Lines...
Page 48: ...Nortec SAM e Installation 44 Figure 8 Long Steam Run...
Page 49: ...45 Nortec SAM e Installation Atmospheric Steam Lines...
Page 57: ...53 Nortec SAM e Installation 3 Fit shields to tubes 4 Secure with stainless straps...
Page 58: ...Nortec SAM e Installation 54 5 Completed tube...
Page 59: ...55 Nortec SAM e Installation Troubleshooting Maintenance Spare Parts...