Operating the Condair DL control software
–
Lower Limit Hum.
: With this setting you set the minimum signal value
in % of the maximum signal value of the humidity sensor, if undershot a
sensor interruption message (Error "E32") is triggered.
Note
: this setting appears only if the "Control Mode" is set to "RH P" or
"RH PI".
Factory setting:
3 %
Options:
0.0 ... 10.0 %
–
Enable Contact
: With this setting you determine whether the enable
contact on the driver board is evaluated ("On") or ignored ("Off") by the
control software.
Factory setting:
On
Options:
On
or
Off
5.3.5 Communication settings in the "Network" submenu
In the "Network" submenu you determine the parameters for digital communication protocols.
5.3.5.1 Accessing the "Network"submenu
Access the "Network" submenu as shown below.
Network