29
Operating the Condair DL control software
5.2.2 Query operating states in the "About" submenu
09/01/2021
DL
07:00 pm
Humidifier Model
DL Type
Software Version
Serial Number
Remain. Ag-Ion Capacity
PS2 Pressure Switch
Y5 Spray Valve
PS5 Nozzle Pressure
Y7 Spray Valve
Traget Ag-Ion Current
Y2 Reserve
Max. Hum. Capacity
Y3 Air Cleaning
Actual Hum. Capacity
Y4 Ext. Pipe Flush
PS4 Inlet Pressure
Y6 Spray Valve
Water Conductivity
Ag-Ion Current
Y1 Inlet Valve
Water Conductivity
Water Temperature
DL
HUM+FC
1111111
0.5 Ah
On
Closed
58.0 psi
Open
0.2 mA
Closed
342 lb/hr
Closed
15 lb/hr
Closed
58.0 psi
Closed
0 µS
0.2 mA
Open
5 uS/cm
50.0 °F
About
Continued on
next page
–
Humidifier Model
: Name of the humidifier model.
–
DL Type
: Device type ("Humidifier"= Humidifier without booster pump,
"Humi FC"= Humidifier with booster pump, "Humi FC - Off"
(Humidifier with deactivated booster pump or frequency converter, respec-
tively)).
–
Software Version
: Actual software versions of the control board ("Device
FW Version", "FrameWork FW Version" and "Bootloader FW Version")
and driver boards ("Driver Board", "Condu. Board", "Ag-Ion Board" and
"RFI Board").
–
Serial Number
: Serial number of the humidification system.
–
Water Conductivity
: Actual conductivity of the supply water in µS/cm.
Note: During the periodical system flushings or if the system is empty the
conductivity is displayed temporarily with 0 µS/cm. Always wait, until the
system is humidifying, before you read the conductivity value!
–
Water Temperature
: Actual temperature of the supply water in °C.
Note: this info field appears only if the "Water Temperature Monitoring" option
is installed and activated in the engineering level of the control software.
–
Remain. Ag-Ion Capacity
: Remaining capacity of the silver cartridge in
Ah.
–
Ag-Ion Current
: Actual current of the silver ionization in mA.
–
Target Ag-Ion Current
: Calculated nominal current for silver ionization
in mA.
–
Max. Capacity
: Maximum humidification capacity in lb/hr.
–
Actual Hum. Capacity
: Actual humidification capacity in lb/hr.
–
PS2 Pressure Switch
: Actual status of the optional pressure switch PS2
when operating the humidification system Condair DL type A with sterile
filter (On= pressure present, Off= no pressure present).
–
PS4 Inlet Pressure
: Actual water inlet pressure in psi.
–
PS5 Nozzle Pressure
: Actual atomization pressure of the water in psi
(Type A with booster pump only).
–
Y1 Inlet Valve
: Actual operating status of the inlet valve "Y1".
–
Y2 Reserve
: no function.
–
Y3 Air Cleaning
: Actual operating status of the external valve "Y3" of the
air cleaning option.
–
Y4 Ext. Pipe Flush
: Actual operating status of the external valve "Y4" of
the external pipe flush option.
–
Y5 Spray Valve
: Actual operating status spray valve "Y5".
–
Y6 Spray Valve
: Actual operating status spray valve "Y6".
–
Y7 Spray Valve
: Actual operating status spray valve "Y7".