39
Operating the Condair DL control software
5.3.3.2 Set the power limitation in the "Operation" submenu
09/01/2021
DL
07:00 pm
Capacity Limitation
100 %
Operation
–
Capacity Limitation
: with this setting you determine the capacity limita-
tion in relation to maximum capacity in %.
Factory setting:
100 %
Setting range:
20 ... 100 %
5.3.3.3 Set the flush timer in the "Flush Timer" submenu
09/01/2021
DL
07:00 pm
Function
Start Time
On
00:00
Flush Timer
–
Function
: with this setting you can activate ("On") or deactivate ("Off")
the timer-controlled flushing of the water system.
Note: during the timer-controlled flushing of the water system, first the
water supply line is flushed via the external pipe flush valve Y4, assumed
your system is equipped with the external pipe flush option. Then, the inlet
valve Y1 opens and the internal water system of the central unit is flushed
via the drain valve Y10 (normally open valve). Finally, the air cleaning
valve Y3 opens, and the spray circuits are blown out one after the other,
assumed your system is equipped with the air cleaning option.
Factory setting:
Off
Optional settings:
Off
or
On
–
Start Time
: with this setting you determine the time of day, at which the
timer-controlled flushing of the water system is to be carried out.
Note: if at the point in time, on which the timer-controlled flushing is to be
carried out, a humidification is in progress, the flushing is omitted.
Factory setting:
00:00
Optional settings:
00:00
to
23:59
5.3.3.4 Activate/deactivate the softstart function in the "Softstart" submenu
09/01/2021
DL
07:00 pm
Softstart
On
Softstart
–
Softstart
: With this setting you activate ("On") or deactivate ("Off") the
softstart function.
Note: The softstart function limits the amount of water sprayed by 50% for
10 minutes when the Condair DL starts humidifying again, provided the
Condair DL has not humidified for more than 30 minutes (factory setting).
Factory setting:
Off
Optional settings:
Off
or
On