21
Control unit
6.
Control Unit
6.1
Adjusting the control unit
6.1.1
Language, time and total hardness quick setting
Proceed as shown in the following table:
6.1.2
Parameter setting
The setting
of cycles (regeneration process) and
parameters
is a necessary prerequisite for the correct operation of the system. The control unit is preset
ex-works to match the size. Check all settings and use the corresponding size-specific tables
in the appendix. These tables contain all the values to be set, including the quick setting from
section 1.1.
Step
Operation
Display content
Starting point
Time of day (for example)
A
7:35
01
Press CLOCK briefly, hour flashes
Set with ▼ or ▲
Hour
Set
8:35
02
Press NEXT briefly, minute flashes
Set with ▼ or ▲
Hour
Set
08:40
03
NEXT
Time of day (for example)
A
8:40
04
NEXT + ▲ press together
and hold briefly
German
Set
Language
05
NEXT + ▼ or ▲
Input hardness (measured value,
for example)
Set
20°dH
06
NEXT + ▼ or ▲
Residual hardness
Set
0°dH
07
NEXT + ▼ or ▲
Days between two regenerations
Set
3
08
NEXT
Time of day (for example)
A
8:41
Summary of Contents for CONDAIR SOFT
Page 31: ...31 Appendix 9 3 Electrical connection...
Page 48: ...48 9 5 1 Soft 60 System drawing Appendix...
Page 49: ...49 9 5 2 Soft 120 System drawing Appendix...
Page 50: ...50 9 5 3 Soft 200 System drawing Appendix...
Page 51: ...51 9 5 4 Soft 320 System drawing Appendix...
Page 52: ...52 9 5 5 Soft 400 System drawing Appendix...
Page 54: ...54 Notes...
Page 55: ...55 Notes...