If you have a TW-2 model, you can automatically start and
stop the Thermolator from a remote switching or timing
device that has power contacts rated 110VAC, such as the
process machine control.
Wiring the device to the Thermolator is accomplished through
a dry contact to the appropriate terminals on the motherboard.
After wiring the device to the unit, Auto Start must be
enabled by configuring a dip switch on the motherboard.
Disconnect and lockout power to the unit.
Open the electrical enclosure.
Punch a small hole in the left side of the
electrical enclosure.
The hole must be large enough to
accommodate conduit for the power contact wires from
your switching or timing device.
Insert the two power leads from the device
through the conduit into the electrical enclosure.
Connect the 110VAC device contact wires to
the Auto Start terminals.
Make sure terminals are
screwed tight.
Thermolator TW-1 and TW-2
UGH015/0100
I
NSTALLING THE
A
UTO
S
TART
F
EATURE
(TW-2 O
NLY
)
3-16
I
NSTALLATION
1
2
3
4
AC IN 4
AC IN + 3
AC OUT 2
AC OUT + 1
F1
LLS/WPS
LLS/WPS
AUT
OST
ART
AUT
OST
ART
HPS/LPS
HPS/LPS
OPS
OPS
F
S
TAT
F
S
TAT
6
5
4
3
2
1
4
3
2
1
5
WARNING: Electric shock hazard
This equipment is powered by high voltage. Always
disconnect and lock out the main power source
before opening the unit or the electrical enclosure to
modify factory settings. Failure to disconnect and
lock out the main power source can result in severe
personal injury.
IMPORTANT:
Always
refer to the wiring diagrams
that came with your tempera-
ture control unit before mak-
ing electrical connections. The
diagrams show the most
accurate electrical component
information.
Device contacts
Continued on next page
Summary of Contents for Thermolater vacuTrac
Page 9: ...Figure 1...
Page 12: ......
Page 15: ......
Page 16: ......
Page 50: ......
Page 62: ......
Page 100: ......
Page 106: ......
Page 117: ...UGH015 0100 TW 1 230 460V WIRING DIAGRAM PD 5...
Page 119: ...UGH015 0100 TW 2 230 460V WIRING DIAGRAM PD 7 2...