UGH015/0100
Thermolator TW-1 and TW-2
S
ELECTING THE
T
EMPERATURE
C
ONTROL
P
OINT
(TW-2
ONLY
)
I
NSTALLATION
3-13
Press the RUN button to save the control point.
◆
◆
The control will display “Pr OFF” to prompt you to
remove power to the unit.
IMPORTANT:
If RUN is not pressed, the new
control point source will not be saved.
Turn off power to the unit.
Disconnect and lock out
the main power supply.
Open the electrical
enclosure.
Set dip switch 5 to
OFF.
Close the electrical enclosure and restore
power to the unit.
The Thermolator will now control the process temperature
based on actual temperatures recorded at the new control
point source.