background image

8

Refrigerant Line Connections

 WARNING:

The coil in the air handler is factory shipped with 

a nitrogen charge. Avoid direct face exposure 

or contact with valve when gas is escaping. 

Always ensure adequate ventilation is present 

during the depressurization process. Address 

any uncertainties before proceeding. Failure 

to comply with this warning could result in 

equipment damage, personal injury, or death.

NITROGEN

HEALTH

FLAMMABILITY

REACTIVITY

0 Minimal Hazard

1 Slight Hazard

1

0

0

•  The  installer  should  make  every  effort  to  ensure  the 

field installed refrigerant containing components of the 

system have been installed in accordance with these 

instructions and sound installation practices for reliable 

system operation and longevity.

•  The air handler coil does not contain a refrigerant charge. 

Refer to the installation instructions supplied with the 

outdoor unit for refrigerant charge information.

•  Always refer to the installation instructions supplied with 

the outdoor unit for piping requirements. The suction 

and liquid lines must be sized in accordance with the 

condensing unit specifications. See Figure 12 (page 

17) for liquid and suction line locations.

•  When  connecting  refrigerant  linesets  together,  it  is 

recommended that dry nitrogen be flowing through the 

joints during brazing. This will prevent internal oxidation 

and scaling from occurring.

•  Refrigerant tubing should be routed in a manner that 

minimizes the length of tubing and the number of bends 

in the tubing. It should be supported in a manner that 

prevents it from vibrating or abrading during system 

operation. Tubing should be kept clean of foreign debris 

during installation.

•  If precise forming of refrigerant lines is required, a copper 

tubing bender is recommended. Avoid sharp bends and 

contact of the refrigerant lines with metal surfaces.

•  Refrigerant  lines  should  be  wrapped  with  pressure 

sensitive neoprene or other suitable material where 

they pass against sharp sheet metal edges.

• 

HMG**F1E, HMG**X1E & HCG**V1E Series air handlers 
are charged through service valves on the end of the 
liquid tube for each circuit. These must be removed 
before brazing the line sets.

7. Insert the plug (from horizontal drain pan) into the open 

and unused drain hole in the drain pan at the bottom 

of the unit to block bypass air.

8. Remove the corresponding drain line knockout from 

the coil access door to allow access to the horizontal 

drain.

9. Replace the door and attach the drain line

Circuit Breaker Cover Installation

The air handler circuit breaker cover is designed to protect 
the breakers of an installed heater kit from debris and 
condensation.The cover attaches to the breaker recess 
of the air handler upper access door using a double-sided 
adhesive gasket. See Figure 5. The heater kit circuit 
breaker toggles are still accessible and can be switched 
with the cover in place.

There are 2 different circuit breaker cover sizes:

•  2-breaker cover for 2, 2.5, 3, 3.5, & 4 ton air handlers.

•  3-breaker cover for 5 ton air handlers.

After the heater kit is properly installed, remove the 
appropriate knockouts in the upper air handler access door 
and follow these instructions to install the breaker cover:

1. Clean any oil, dirt, or insulation fibers from the recess 

area of the air handler access door. This step is important 

for ensuring the gasket adheres properly to the sheet 

metal door.

2. Remove release paper from one side of the gasket 

and attach to back side of the breaker cover. 

NOTE:

 For proper alignment, It is recommended to leave 

the center section of the gasket in place when attaching 

the gasket to the breaker cover. Remove the center 

section after the gasket is applied to the breaker cover.

Circuit Brea

ker

Cover

Circuit

Breakers

Recess

Air Handler A

ccess Door

Figure 5. Circuit Breaker Cover

3. Remove the release paper from the other side of the 

gasket and attach to the circuit breaker recess area.

4. Press firmly along all four sides of the cover to ensure 

gasket and cover are securely attached to the access 

door.

Summary of Contents for HCG V1E Series

Page 1: ...e adjustment or maintenance may cause explosion fire electrical shock or other hazardous conditions which may result in personal injury or property damage Unless otherwise noted in these instructions...

Page 2: ...nuously 14 Selecting Continuous Low Spd Fan Operation 14 Turning the Blower Off 14 System Cooling 14 System Heating 14 Selecting minimum Electric Heat Airflow 14 Blower Configurations 14 Determining N...

Page 3: ...Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could result in possible damage to the equipment serious p...

Page 4: ...s may require additional clearance to equipment Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums should be considered in the...

Page 5: ...ely sized to the return air duct opening or filter rack located in the bottom of the unit Accessing the filter does not require tools and can be removed from the front of the unit by removing the filt...

Page 6: ...r installations require a 1 4 thick noncombustible resilient gasket to be used whenever the supplyorreturnairductspassthroughthefloor Thegasket should be positioned between the duct unit and floor Upf...

Page 7: ...of the unit to block bypass air 4 Remove the corresponding drain line knockout from the coil access door to allow access to the horizontal drain 5 Replace the door and attach the drain line Horizonta...

Page 8: ...er suitable material where they pass against sharp sheet metal edges HMG F1E HMG X1E HCG V1ESeriesairhandlers are charged through service valves on the end of the liquid tube for each circuit These mu...

Page 9: ...rform steps 1 9 to confirm that the orifice size meets the requirements outlined in the outdoor unit installation manual 1 Remove the cap from the end of the liquid line 2 Verify pressurization by dep...

Page 10: ...ld maintain a minimum horizontal slope in the direction of discharge of not less than 1 vertical for every 10 ft of horizontal run If the air handler is located in or above a living space where damage...

Page 11: ...ine voltage power supply to this unit Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit Aluminum supply wire may be used if a heater kit is inst...

Page 12: ...ling See Figures 14 or 15 page 23 and Table 12 pages 29 31 for control board modes and actions Twinning HMG F1E series air handler s are not supplied with a built in twinning capability To connect two...

Page 13: ...stallation instructions included with the kit Wire the humidistat through the low voltage wire entrance in the air handler to the control board terminal marked DEHUM Wirethehumidistattoopenonriseinhum...

Page 14: ...the register s Ensure that there are no obstructions at the registers or in the ducts Selecting continuous low speed fan operation Standard Blower The air handler is equipped with an option of contin...

Page 15: ...rflow setting will increase the energy efficiency and capacity but will also decrease the supply air temperature For maximum capacity and energy efficiency select an airflow at or near the top of the...

Page 16: ...g affected by drafts or heat from lamps or other appliances To achieve the best performance and minimize equipment failure it is recommended that a yearly maintenance checkup be performed At a minimum...

Page 17: ...5 8 17 8 11 4 3 1 4 2 5 8 11 8 K O typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W 1 1 8 1 7 8 7 8 K O H 22 A FURNACE SIZE BTUH H W A Detail D 24K 30K 43 5 16 14 3 1...

Page 18: ...Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Motor Control Board Control Board Filter Door Upper Door Assembly Lower Door...

Page 19: ...03 0 15 0 28 0 41 0 54 0 68 High 1427 1385 1333 1270 1196 1113 1018 913 Corrected ESP1 0 00 0 00 0 00 0 09 0 23 0 36 0 50 0 64 HMG42F1E Low 1324 1302 1271 1233 1187 1134 1072 1003 Corrected ESP1 0 00...

Page 20: ...50 1 1 1 0 1155 1105 1060 1010 965 920 870 825 0 0 0 1 1230 1185 1140 1090 1045 1010 965 920 1 0 0 1 1285 1260 1210 1165 1125 1080 1040 1010 0 1 0 1 1330 1290 1245 1205 1170 1125 1085 1045 1 1 0 1 139...

Page 21: ...0 1 1 4 TON 700 0 1 0 0 1350 0 1 0 0 750 0 1 0 1 1400 0 1 0 1 800 0 1 1 0 2 5 TON 1450 0 1 1 0 850 0 1 1 1 1500 0 1 1 1 875 1 0 0 0 1550 1 0 0 0 950 1 0 0 1 1600 1 0 0 1 5 TON 1050 1 0 1 0 3 TON 1650...

Page 22: ...750 1 20 1500 1 0 1 1 0 800 1 25 n a 1 0 1 1 1 850 1 30 n a 1 1 0 0 0 875 1 1 0 0 1 950 1 1 0 1 0 1050 1 1 0 1 1 1150 1 1 1 0 0 1250 1 1 1 0 1 1350 1 1 1 1 0 1400 1 1 1 1 1 1600 HCG48V1E HCG60V1E Cool...

Page 23: ...TC_R HEAT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 C R G Y2 Y O 1W 2W 1Y L LED 1 HEATER P1 L 2 HUM EAC P2 3A Fuse P3 Figure 14 Single Stage Control Board Figure 15 Two Stage Control Board ELECT...

Page 24: ...W C EXPANSION PORT R RED GREEN TEST PORT BLOWER MOTOR RED INPUTS COOL HEAT FAN SPEED OUTPUTS STATUS LIGHTS 2 3 4 5 6 7 8 OFF ON A B GREEN RED STATUS NOT USED TEST PORT BLOWER MOTOR R C Y1 TWIN DEHUM...

Page 25: ...PLUG HOUSING WHEN HEATER KIT NOT INSTALLED BLACK RED WHITE BROWN BROWN BLACK WHITE RED GRAY YELLOW WHITE GREEN GRAY RED NOTES 1 The blower motor speed tap connection may not be as shown See the Instal...

Page 26: ...BLACK WHITE GRAY RED BLACK RED WHITE BLACK MOTOR 6 PIN PLUG HARNESS WHITE BLACK BLUE GREEN YELLOW ORANGE RED BROWN BLUE GREEN ORANGE RED BROWN YELLOW CUT WIRES TO REMOVE PLUG HOUSING WHEN HEATER KIT N...

Page 27: ...R BLACK WHITE 6 PIN PLUG 6 PIN PLUG BLACK WHITE BLACK WHITE GRAY RED BLACK HARNESS HARNESS GREEN BROWN RED ORANGE YELLOW GREEN BLUE BROWN RED ORANGE YELLOW GREEN BLUE RED CUT WIRES TO REMOVE PLUG HOUS...

Page 28: ...009Q XX 29 7 30 26 1 30 015Q XX 45 9 50 40 2 45 HMG42F1E None 3 1 3 1 15 15 3 1 3 1 15 15 005H XX 28 1 28 1 30 30 24 8 24 8 25 25 008H XX 42 7 42 7 45 45 37 4 37 4 40 40 010H XX 53 1 53 1 60 60 46 5...

Page 29: ...B CIRCUIT C SINGLE CIRCUIT CIRCUIT A CIRCUIT B CIRCUIT C SINGLE CIRCUIT CIRCUIT A CIRCUIT B CIRCUIT C SINGLE CIRCUIT CIRCUIT A CIRCUIT B CIRCUIT C SINGLE CIRCUIT HMG24X1E HMG30X1E HCG24V1E HCG30V1E No...

Page 30: ...seconds delay Stage 3 Heat on after 10 seconds delay Stage 4 Heat on after 15 seconds delay Stage 5 Heat on after 20 seconds delay Stage 6 Heat on after 25 seconds delay OFF Heat stages off instantly...

Page 31: ...econd delay Stage 2 Heat on after 5 seconds delay Stage 3 Heat on after 10 seconds delay Stage 4 Heat on after 15 seconds delay Stage 5 Heat on after 20 seconds delay 30 KW Stage 1Heat on instantly Co...

Page 32: ...ing common sense plays an important role as well Pay attention to all safetywarningsandanyotherspecialnoteshighlightedinthemanual Improper installation of the air handler or failure to follow safety w...

Reviews: