NOTE:

 Variable speed air handlers cannot be twinned.

Heater Kits

When electric heat packages with circuit breakers are 
field-installed, the circuit breaker may be used as a 
disconnecting means in most applications. Reference 
the NEC and local codes for disconnect requirements.

If a heater kit is installed:
The HMG**F1E series air handler is shipped from the 
factory without an electric heater kit installed. If Electric 
heat is desired, the H6HK heater kit may be purchased 
separately and field installed. Determine the correct size 
heater kit for your unit by referring to the list below or the 
units rating label.

24K & 30K BTUH ........................................... 15Kw max
36K & 42K BTUH ........................................... 20Kw max
48K & 60K BTUH ........................................... 30Kw max

1. Connect the 2 wire plug of the air handler to the mating 

2 wire plug of the heater kit.

2. Connect the line voltage leads to the circuit breaker or 

terminal block provided.

3. Connect the heater kit plug with the mating receptacle 

on the air handler control board.

If a heater kit is not installed:

1. Remove the 2 wire plug of the air handler by cutting the 

wires and discarding the plug.

2. Strip the ends of the 2 air handler wires and connect 

to the line-voltage leads with the 2 wire nuts provided. 

Electronic Air Cleaner (EAC)

The unit has an output to power an electronic air cleaner 
when the blower is running. This output is rated to 1.0 
amp at 208/240V.

Humidifier

The unit has an output to power a humidifier when the 
blower is running. This output is rated to 1.0 amp at 
208/240V.

Optional Humidistat

(HMG**X1E & HCG**V1E Models Only)
The optional humidistat may be installed in the return air 
duct to provide excellent humidity control when needed 
and maximum system capacity and energy efficiency when 
humidity levels are normal. The humidistat senses when 
humidity in the return air stream is above a preset level 
(field adjustable) and sends a signal to the motor to reduce 
the airflow so that more moisture may be removed until the 
humidity level drops. The air handler is pre-programmed 
for humidistat operation.

Install the humidistat in the return air duct as directed in 
the installation instructions included with the kit. Wire the 
humidistat through the low-voltage wire entrance in the 
air handler to the control board terminal marked 

DEHUM

Wire the humidistat to open on rise in humidity. See Figures 
16 & 17 (page 24).

STARTUP & ADJUSTMENTS

 WARNING:

The evaporator coil is shipped from the factory 

with a nitrogen charge. Use caution when 

preparing coils for field connections. If repairs 

make it necessary for evacuation and charging, 

it should only be attempted by qualified, 

trained personnel thoroughly familiar with this 

equipment. Some local codes require licensed 

installation service personnel to service this 

type of equipment. Under no circumstances 

should the equipment owner attempt to install 

and/or service this equipment. Failure to comply 

with this warning could result in equipment 

damage, personal injury, or death.

NITROGEN

HEALTH

FLAMMABILITY

REACTIVITY

0 Minimal Hazard

1 Slight Hazard

1

0

0

Before You Start the Unit

Prior to start-up, complete the following inspections:

  Verify the unit is level and properly located with adequate 

clearances for servicing the unit. See Table 1 (page 4).

 Check condensate drain line(s) for proper drainage.

 Verify the surrounding area and top of the unit is free 

from obstructions and debris.

 Check all duct connections. Make sure the duct work 

is adequately sealed to prevent air leakage.

 Check all coil connections for leaks.

 Verify that the line voltage power leads are securely 

connected and the unit is properly grounded. Make sure 

all doors are installed before restoring power to the unit

  Verify the thermostat is wired correctly. Make sure all 

low voltage wires are securely connected.

 Verify the power supply branch circuit overcurrent 

protection is sized properly.

 Verify filter is properly and securely installed.

IMPORTANT:

 Before starting the unit, install the initial 

charge on units that are factory shipped with a nitrogen 
holding charge:

1. Read all installation instructions first.

2. Purge the nitrogen holding charge.

3. Evacuate the unit to 350 - 500 microns.

4. Allow the unit to remain under vacuum for at least 30 

minutes.

5. Weigh in the proper amount of new (or reclaimed) 

refrigerant. Refer to the air conditioner or heat pump  

installation manual for the proper type and quantity of 

refrigerant.

Summary of Contents for HCG V1E Series

Page 1: ...e adjustment or maintenance may cause explosion fire electrical shock or other hazardous conditions which may result in personal injury or property damage Unless otherwise noted in these instructions...

Page 2: ...nuously 14 Selecting Continuous Low Spd Fan Operation 14 Turning the Blower Off 14 System Cooling 14 System Heating 14 Selecting minimum Electric Heat Airflow 14 Blower Configurations 14 Determining N...

Page 3: ...Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could result in possible damage to the equipment serious p...

Page 4: ...s may require additional clearance to equipment Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums should be considered in the...

Page 5: ...ely sized to the return air duct opening or filter rack located in the bottom of the unit Accessing the filter does not require tools and can be removed from the front of the unit by removing the filt...

Page 6: ...r installations require a 1 4 thick noncombustible resilient gasket to be used whenever the supplyorreturnairductspassthroughthefloor Thegasket should be positioned between the duct unit and floor Upf...

Page 7: ...of the unit to block bypass air 4 Remove the corresponding drain line knockout from the coil access door to allow access to the horizontal drain 5 Replace the door and attach the drain line Horizonta...

Page 8: ...er suitable material where they pass against sharp sheet metal edges HMG F1E HMG X1E HCG V1ESeriesairhandlers are charged through service valves on the end of the liquid tube for each circuit These mu...

Page 9: ...rform steps 1 9 to confirm that the orifice size meets the requirements outlined in the outdoor unit installation manual 1 Remove the cap from the end of the liquid line 2 Verify pressurization by dep...

Page 10: ...ld maintain a minimum horizontal slope in the direction of discharge of not less than 1 vertical for every 10 ft of horizontal run If the air handler is located in or above a living space where damage...

Page 11: ...ine voltage power supply to this unit Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit Aluminum supply wire may be used if a heater kit is inst...

Page 12: ...ling See Figures 14 or 15 page 23 and Table 12 pages 29 31 for control board modes and actions Twinning HMG F1E series air handler s are not supplied with a built in twinning capability To connect two...

Page 13: ...stallation instructions included with the kit Wire the humidistat through the low voltage wire entrance in the air handler to the control board terminal marked DEHUM Wirethehumidistattoopenonriseinhum...

Page 14: ...the register s Ensure that there are no obstructions at the registers or in the ducts Selecting continuous low speed fan operation Standard Blower The air handler is equipped with an option of contin...

Page 15: ...rflow setting will increase the energy efficiency and capacity but will also decrease the supply air temperature For maximum capacity and energy efficiency select an airflow at or near the top of the...

Page 16: ...g affected by drafts or heat from lamps or other appliances To achieve the best performance and minimize equipment failure it is recommended that a yearly maintenance checkup be performed At a minimum...

Page 17: ...5 8 17 8 11 4 3 1 4 2 5 8 11 8 K O typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W 1 1 8 1 7 8 7 8 K O H 22 A FURNACE SIZE BTUH H W A Detail D 24K 30K 43 5 16 14 3 1...

Page 18: ...Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Motor Control Board Control Board Filter Door Upper Door Assembly Lower Door...

Page 19: ...03 0 15 0 28 0 41 0 54 0 68 High 1427 1385 1333 1270 1196 1113 1018 913 Corrected ESP1 0 00 0 00 0 00 0 09 0 23 0 36 0 50 0 64 HMG42F1E Low 1324 1302 1271 1233 1187 1134 1072 1003 Corrected ESP1 0 00...

Page 20: ...50 1 1 1 0 1155 1105 1060 1010 965 920 870 825 0 0 0 1 1230 1185 1140 1090 1045 1010 965 920 1 0 0 1 1285 1260 1210 1165 1125 1080 1040 1010 0 1 0 1 1330 1290 1245 1205 1170 1125 1085 1045 1 1 0 1 139...

Page 21: ...0 1 1 4 TON 700 0 1 0 0 1350 0 1 0 0 750 0 1 0 1 1400 0 1 0 1 800 0 1 1 0 2 5 TON 1450 0 1 1 0 850 0 1 1 1 1500 0 1 1 1 875 1 0 0 0 1550 1 0 0 0 950 1 0 0 1 1600 1 0 0 1 5 TON 1050 1 0 1 0 3 TON 1650...

Page 22: ...750 1 20 1500 1 0 1 1 0 800 1 25 n a 1 0 1 1 1 850 1 30 n a 1 1 0 0 0 875 1 1 0 0 1 950 1 1 0 1 0 1050 1 1 0 1 1 1150 1 1 1 0 0 1250 1 1 1 0 1 1350 1 1 1 1 0 1400 1 1 1 1 1 1600 HCG48V1E HCG60V1E Cool...

Page 23: ...TC_R HEAT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 C R G Y2 Y O 1W 2W 1Y L LED 1 HEATER P1 L 2 HUM EAC P2 3A Fuse P3 Figure 14 Single Stage Control Board Figure 15 Two Stage Control Board ELECT...

Page 24: ...W C EXPANSION PORT R RED GREEN TEST PORT BLOWER MOTOR RED INPUTS COOL HEAT FAN SPEED OUTPUTS STATUS LIGHTS 2 3 4 5 6 7 8 OFF ON A B GREEN RED STATUS NOT USED TEST PORT BLOWER MOTOR R C Y1 TWIN DEHUM...

Page 25: ...PLUG HOUSING WHEN HEATER KIT NOT INSTALLED BLACK RED WHITE BROWN BROWN BLACK WHITE RED GRAY YELLOW WHITE GREEN GRAY RED NOTES 1 The blower motor speed tap connection may not be as shown See the Instal...

Page 26: ...BLACK WHITE GRAY RED BLACK RED WHITE BLACK MOTOR 6 PIN PLUG HARNESS WHITE BLACK BLUE GREEN YELLOW ORANGE RED BROWN BLUE GREEN ORANGE RED BROWN YELLOW CUT WIRES TO REMOVE PLUG HOUSING WHEN HEATER KIT N...

Page 27: ...R BLACK WHITE 6 PIN PLUG 6 PIN PLUG BLACK WHITE BLACK WHITE GRAY RED BLACK HARNESS HARNESS GREEN BROWN RED ORANGE YELLOW GREEN BLUE BROWN RED ORANGE YELLOW GREEN BLUE RED CUT WIRES TO REMOVE PLUG HOUS...

Page 28: ...009Q XX 29 7 30 26 1 30 015Q XX 45 9 50 40 2 45 HMG42F1E None 3 1 3 1 15 15 3 1 3 1 15 15 005H XX 28 1 28 1 30 30 24 8 24 8 25 25 008H XX 42 7 42 7 45 45 37 4 37 4 40 40 010H XX 53 1 53 1 60 60 46 5...

Page 29: ...B CIRCUIT C SINGLE CIRCUIT CIRCUIT A CIRCUIT B CIRCUIT C SINGLE CIRCUIT CIRCUIT A CIRCUIT B CIRCUIT C SINGLE CIRCUIT CIRCUIT A CIRCUIT B CIRCUIT C SINGLE CIRCUIT HMG24X1E HMG30X1E HCG24V1E HCG30V1E No...

Page 30: ...seconds delay Stage 3 Heat on after 10 seconds delay Stage 4 Heat on after 15 seconds delay Stage 5 Heat on after 20 seconds delay Stage 6 Heat on after 25 seconds delay OFF Heat stages off instantly...

Page 31: ...econd delay Stage 2 Heat on after 5 seconds delay Stage 3 Heat on after 10 seconds delay Stage 4 Heat on after 15 seconds delay Stage 5 Heat on after 20 seconds delay 30 KW Stage 1Heat on instantly Co...

Page 32: ...ing common sense plays an important role as well Pay attention to all safetywarningsandanyotherspecialnoteshighlightedinthemanual Improper installation of the air handler or failure to follow safety w...