InteliLite
NT
– MRS3,4, AMF8,9, SW version 1.4, ©ComAp – October 2008 60
IL-NT-MRS3,4-AMF8,9-1.4-Reference Guide.pdf
Voltage
supply
8-36V
DC
Consumption
40-430mA depend on supply voltage and temperature
Consumption depends on supply voltage
0,104A at 8VDC
0,080A
at
12VDC
0,051A
at
24VDC
0,044A
at
30VDC
0,040A at 36VDC
Allowed supply voltage drop-out:
100ms from min. 10V, return to min. 8V
Battery voltage measurement tolerance
2 % at 24V
Hint:
For the supply voltage less than 7V the backlight of the display is switched off.
Short-term voltage drops (e.g. during the engine cranking) do not affect the operation at all.
Operating conditions
Operating temperature IL-NT
-20..+70
o
C
Operating temperature IL-NT LT
#
-40..+70
o
C
Storage
temperature
-30..+80
o
C
Protection front panel
IP65
Humidity 95%
without
condensation
Standard conformity
Low Voltage Directive
EN 61010-1:95 +A1:97
Electromagnetic Compatibility
EN 50081-1:94, EN 50081-2:96
EN
50082-1:99,
EN
50082-2:97
Vibration
5 - 25 Hz, ±1,6mm
25 - 100 Hz, a = 4 g
Shocks
a
=
200
m/s
2
Dimensions and weight
Dimensions
180x120x55mm
Weight
450g
Mains and generator
Nominal
frequency
50-60Hz
Frequency measurement tolerance
0,2Hz
Current inputs
Nominal input current (from CT)
5 A
Load (CT output impedance)
< 0,1
Ω
CT input burden
< 0,2 VA per phase (In=5A)
Max. measured current from CT
10 A
Current measurement tolerance
2% from the Nominal current
Max. peak current from CT
150 A / 1s
Max. continuous current
12 A
Voltage inputs
Measuring voltage range
0 – 277 VAC phase to neutral
0 – 480 VAC phase to phaseMaximal measured
voltage 340 VAC phase to neutral
600
VAC
phase
to
phase
Input
resistance 0.6
M
Ω
phase to phase
0.3 M
Ω
phase to neutral