InteliLite
NT
– MRS3,4, AMF8,9, SW version 1.4, ©ComAp – October 2008 62
IL-NT-MRS3,4-AMF8,9-1.4-Reference Guide.pdf
•
3084A DeviceBus for Allen-Bradley DeviceNet
•
3085A DeviceBus for Allen-Bradley DeviceNet
•
3105A Paired EIA Industrial RS485 cable
LAPP CABLE (see
http://www.lappcable.com
)
•
Unitronic BUS DeviceNet Trunk Cable
•
Unitronic BUS DeviceNet Drop Cable
•
Unitronic BUS CAN
•
Unitronic-FD BUS P CAN UL/CSA
IL-NT RS232 interface (optional card)
Plugs into IL-NT controller COMMUNICATIN MODULE port.
Maximal
distance
10m
Maximum Speed
Up to 57.6 kBd (DIRECT)
Recommend external converter:
ADVANTECH – ADAM 4520: RS232 to RS422/485 converter, DIN rail, automatic RS485 bus
supervision, no external data flow control signals, galvanic isolated.
Recommended internal converter:
ADVANTECH – PCL-745B or PCL745S : Dual port RS422/485 Interface card, automatic RS485 bus
supervision, no external data flow control signals, galvanic isolated
Hint:
For details on all IL-NT extension and communication modules see IL-NT, IC-NT-Accessory Modules
manual.
IL-NT RS232-485 interface (optional card)
Plugs into IL-NT controller COMMUNICATIN MODULE port.
Maximal distance
10m (RS232), 1200m (RS485)
Maximum Speed
Up to 57.6 kBd (DIRECT)
IL-NT S-USB interface (optional card)
Plugs into IL-NT controller COMMUNICATIN MODULE port.
Maximal
distance
5m
Maximum Speed
Up to 57.6 kBd (DIRECT)
Use only shielded A-B USB cables up to 5m length.
Recommend USB cable:
USB-LINK CABLE 1.8M– ComAp A-B USB cable.
IL-NT AOUT8 interface (optional card)
Plugs into IL-NT controller EXTENSION MODULE port.
Number of PWM outputs
8
PWM
frequency 250Hz
Maximum
current
0.5
A