Events specification
Protection
type
Information on binary
output available (See
list of
Binary outputs
)
Description
parameter. The controller stays in
INIT mode. Check all parameters,
write at least one new parameter.
Fgen <
SD
YES
The generator frequency is below limit
given by 75% of
Nominal freq
setpoint.
Overspeed
SD
NO
The protection comes active if the
speed is greater than 115% of value
equal to 30*
Nominal freq.
setpoint.
Underspeed
SD
YES
During starting of the engine when the
RPM reaches the value of
Starting
RPM(= 25% of Nominal RPM)
setpoint the starter is switched off and
the speed of the engine can drop
under
Start RPM
again. Then the
Underspeed protection becomes
active. Protection evaluation starts 5
seconds after reaching
StartingRPM
.
EmergencyStop
SD
NO
If the input
Emergency Stop
is opened
shutdown is immediately activated.
Stop Failed
SD
YES
Gen-set stop failed.
ChargeAlt Fail
WRN
YES
Failure of alternator for charging the
battery.
Wrn ECU Alarm
WRN
NO
*ECU alarm list is not empty