InteliLite
NT
– MRS3,4, AMF8,9, SW version 1.4, ©ComAp – October 2008 51
IL-NT-MRS3,4-AMF8,9-1.4-Reference Guide.pdf
Setpoints of AMF9:
Name Firmware
ver.
Application
Date
App.
ver.
Ser.
num.
Filename
IL-NT
IL-NT-1.4
R:21.10.2008 AMF9
31.10.2008
1,4
12345678
IL-NT-AMF9-1.4.AIL
Group Name
Value Dimension
Password
Com.
obj. Low
limit
High
limit
Data type
Basic
Settings
Gen-set Name
IL-NT
No
8637
Short string
Basic
Settings
CT Ratio
300 /5A
Yes
8274
1
5000 Unsigned 16
Basic
Settings
Nominal Freq
50 Hz
Yes
8278
45
65 Unsigned 16
Basic
Settings
Prestart Time
2 s
No
8394
0
600 Unsigned 16
Basic
Settings
MaxCrank Time
5 s
No
8256
1
60 Unsigned 8
Basic
Settings
Cooling Time
30 s
Yes
8258
0
3600 Unsigned 16
Basic
Settings
AI1 Wrn
2,0 Bar
Yes
8369
-10,0
1000,0 Integer 16
Basic
Settings
AI1 Sd
1,0 Bar
Yes
8370
-10,0
1000,0 Integer 16
Basic
Settings
AI1 Del
3 s
Yes
8365
0
900 Unsigned 16
Basic
Settings
AI2 Wrn
80 °C
Yes
8375
-100
10000 Integer 16
Basic
Settings
AI2 Sd
90 °C
Yes
8376
-100
10000 Integer 16
Basic
Settings
AI2 Del
5 s
Yes
8371
0
900 Unsigned 16
Basic
Settings
Batt Undervolt
11,5 V
Yes
8387
8,0
40,0 Integer 16
Basic
Settings
Test Period
0 d
Yes
10044
0
240 Unsigned 16
Basic
Settings
Test Duration
0 min
Yes
10201
0
240 Unsigned 16
AMF
Settings
EmergStart Del
5 s
No
8301
0
6000 Unsigned 16
AMF
Settings
MainsReturnDel 20 s
No
8302
1
3600
Unsigned
16
AMF
Settings
Mains >V
255 V
No
8305
140
300 Unsigned 16
AMF
Settings
Mains <V
140 V
No
8307
50
255 Unsigned 16
AMF
Settings
Mains >Freq
102,0 %
No
8310
98,0
150,0 Unsigned 16
AMF
Settings
Mains <Freq
98,0 %
No
8312
50,0
102,0 Unsigned 16
Values of AMF9:
Name Firmware
ver.
Application
Date
App.
ver.
Ser. num.
Filename
IL-NT
IL-NT-1.4
R:21.10.2008 AMF9
31.10.2008
1,4
12345678
IL-NT-AMF9-
1.4.AIL
Group Name
Value Dimension
Com.
obj.
Data type
Engine RPM
1500 RPM
8209 Unsigned
16
Engine
ECU State
[010]
10034 Binary 8
Engine
Fuel Rate ECU
0,0 L/h
9860 Unsigned
16
Engine
Cool Temp ECU
22 °C
9855 Integer 16
Engine
IntakeTemp ECU
20 °C
9878 Integer 16