Inputs and Outputs
For Inputs/Outputs overview table see chapter Technical Data.
N
OTE
:
Any Binary input or output can be configured to any IA-NT controller terminal or changed to different
function by LiteEdit software. There is fix 1 sec delay when any binary input is configured as
protection.
Not Used
Binary input has no function. Use this configuration when Binary input is not connected.
Alarm
If the input is closed (or opened) selected alarm is activated.
Binary Alarm configuration items
Name
14 characters ASCII string
NC Normally
closed
Contact type
NO Normally
opened
Warning
Alarm type
Trip
All the time
Valid if checkbox “Engine running
only” is not checked
Alarm active
Engine running only
Valid if checkbox “Engine running
only” is checked
Control
Use this setting to configure the desired function from the list below.