PWR, SW version 1.0, ©ComAp – March 2009
5
IA-NT- PWR-1.0-Reference Guide R1.pdf
General Guidelines
What is in this manual?
This manual describes the InteliATS
NT
PWR (IA-NT-PWR) software, which is designed for automatic
transfer switch applications and provides general information on how to install and operate the
InteliATS
NT
controller.
This manual is dedicated for
•
Automatic transfer switch panel builders
•
Operators of remote gen-sets (started remotely from InteliATS
NT
)
•
For everybody who is concerned with installation, operation and maintenance of the gen-set
InteliATS controller SW and HW versions compatibility
Software InteliATS
NT
v. 1.0 is compatible with the InteliATS
NT
hardware v. 1.3.
There are two modifications of the InteliATS
NT
HW - STD and PWR and two modifications of the
InteliATS
NT
SW – STD and HW which together with the appropriate archive file (IA-NT-STD-X.X.AIL or
IA-NT-PWR-X.X.AIL) form the InteliATS
NT
PWR or STD controller.
Beside that the InteliATS
NT
1.0 software is compatible with IL-NT AMF HW 1.3 too, which is used
when a low temperature ATS application is needed. In this case the InteliATS
NT
SW must be
combined (purchased) with the IL-NT AMF 25 LT HW to obtain the low temperature ATS controller.
N
OTE
:
Because of large variety of InteliATS
NT
parameters settings, it is not possible to describe any
combination. Some of InteliATS
NT
functions are subject of changes depend on SW version.
The data in this manual only describes the product and are not warranty of performance or
characteristic.
C
AUTION
!
SW and HW must be compatible (e.g. IA-NT firmware and IA-NT HW) otherwise the function will be
disabled. If wrong software is downloaded, message HARDWARE INCOMPATIBLE appears on
controller screen. In this case use Boot load (jumper) programming – close Boot jumper and follow
instructions in LiteEdit, download correct software
.
N
OTE
:
ComAp
believes that all information provided herein is correct and reliable and reserves the right to
update at any time. ComAp does not assume any responsibility for its use unless otherwise expressly
undertaken.
W
ARNING
!
Remote control -
InteliATS
NT
controller can be remotely controlled. In case of the work on the
controlled devices check, that nobody can perform remote operation.To be sure disconnect
- remote control via RS232 line
- input REM TRANSFER
- input REMOTE AUT
- input REMOTE TEST
or disconnect output Rem START/STOP and outputs GCB CLOSE/OPEN and MCB CLOSE/OPEN