InteliATS
NT
PWR, SW version 1.0, ©ComAp – March 2009
31
IA-NT- PWR-1.0-Reference Guide R1.pdf
Binary outputs IA-NT - default
BO1 GenStart/Stop
BO2 Alarm
BO3 GCB Close/Open
BO4 MCB Close/Open
BO5
Ready To AMF
BO6 AL Mains Fail
BO7 AL Start Fail
Binary outputs - list
Not Used
Output has no function.
GenStart/Stop
The closed relay sends remote start signal to the gen-set. Generator protections are blocked when the
output is inactive and the GCB is blocked too. Output can be inverted (CLOSE-OFF) using
Basic
Settings: GenStart Logic
setpoint.
Prestart
The output closes when the gen-set start is requested and opens after the
AMF Settings
:
Prestart
Time
has elapsed. Afterwards the
GenStart/Stop
output is activated as a start signal for the remote
gen-set.
Pretransfer
Is activated during the Prestart phase when the Mains Fail had occurred and the gen-set start is the
result of this event. See the
AMF Settings
:
Prestart Time
setpoint for more info.
Alarm
The output closes if :
•
any alarm comes up or
The output opens if
•
FAULT RESET is pressed
The output closes again if a new fault comes up.
GCB Close/Open
The output controls the generator circuit breaker.
N
OTE
:
Supposed time to close (reaction time) of GCB is 0.1 sec.
GCB ON Coil
The output activates Generator Circuit Breaker coil.
GCB OFF Coil
The output deactivates Generator Circuit Breaker coil.