short current alarm activates.
The output opens, if
•
Alarm is not active and
•
FAULT RESET is pressed
AL BatteryFail
Output closes when IA-NT performs reset during start procedure (probably due to weak battery) or
when battery under/over voltage warning appears.
The output opens, if
•
alarm is not active and
•
FAULT RESET is pressed
AL Common Wrn
Output closes when any warning alarm appears.
The output opens, if
•
No warning alarm is active and
•
FAULT RESET is pressed
AL Common Trip
Output closes when any trip alarm appears.
The output opens, if
•
No trip alarm is active and
•
FAULT RESET is pressed
Mode OFF
The output is closed, if OFF Mode is selected.
Mode MAN
The output is closed, if MAN Mode is selected.
Mode AUT
The output is closed, if AUT Mode is selected.
Mode TEST
The output is closed, if TEST mode is selected.
The output opens, if
•
Alarm is not active and
•
FAULT RESET is pressed
Exerc Timer 1
Output activates when Timer 1 is active. Simultaneously, gen-set is started when it is in AUT mode.
Exerc Timer 2
Output activates when Timer 2 is active. Simultaneously, gen-set is started when it is in AUT mode.
Not In AUT
Output activates when the controller is not in AUT mode.
Neutral Pos
Switches ATS switch to its neutral position.
Neutral Coil
Activates the neutral position coil of the ATS switch.