InteliATS
NT
PWR, SW version 1.0, ©ComAp – March 2009
46
IA-NT- PWR-1.0-Reference Guide R1.pdf
N
OTE
:
The target address (GSM phone number or e-mail address) must be set correctly to the setpoint(s)
TelNo/Addr Ch1 resp. TelNo/Addr Ch2.
Red Alarm Msg
[DISABLED, ENABLED]
Set this setpoint to YES if you want to get messages when a
red
(shutdown) alarm occurs.
N
OTE
:
The target address (GSM phone number or e-mail address) must be set correctly to the setpoint(s)
TelNo/Addr Ch1 resp. TelNo/Addr Ch2.
TelNo/Addr Ch1, 2
Enter either a valid GSM phone number or e-mail address to this setpoint, where the alarm messages
shall be sent. Type of active call is considered from the value of this parameter. If it consist „@“ it is
supposed to be e-mail address and active e-mail is sent. If the value is number, without „@“, it is
supposed to be the telephone number and active SMS is sent.
N
OTE
:
For GSM numbers use either national format (i.e. like number you will dial if you want to make a local
call) or full international format with "+" character followed by international prefix in the begining.
This setpoint can be modified from PC only!