SECTION 5
Page 20
5.10.2
(continued)
2.
The remote supply tank must be bolted with stainless
steel bolts and washers to the appropriate support.
It must be equipped with a cut-off valve.
3.
The remote tank and stove shall be connected by a
continuous length, with no splices or joints, of Aeroquip
Hose No. 2651-5, protected with Aeroquip Fire Sleeve No.
624-12. The hose assembly shall be assembled in accordance
with the following diagram, using fittings indicated.
indicated.
4.
No substitutions whatsoever should be made.
5.
After the assembly of the stove and tank are completed
perform the following tests.
a.
Close the valve on the tank. Pump air pressure to
10 psi and observe the pressure gauge for
possible tank leaks.
b.
If no leaks are observed in test "a"
above, then with all valves on the stove
closed the valve on the tank shall be
opened and the pressure drop noted after
five (5) minutes. This small (approximately
one lb.) pressure drop is caused by air
filling the system and is expected. The
tank/stove system shall be left with this
pressure applied for a minimum period of
five (5) hours.
c.
During the final inspection the following tests
shall be made of the stove/tank system.
Summary of Contents for Coronado 25
Page 1: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......