Table C-2:  R7184 Troubleshooting 

continued from previous page

 

Procedure Status 

Corrective 

Action 

Indicator light turns off. 

Eliminate external light source or permanently shield cad cell. 

4. Shield cad cell from 

external light. 

Indicator light stays on. 

4.  Replace cad cell with new cad cell and recheck. 
5.  If indicator light does not turn off, remove cad cell lead 

wires from R7184 and recheck. 

6.  If indicator light turns off, replace cad cell bracket 

assembly. 

7.  If indicator light does not turn off, replace controller. 

Burner starts. 

Trouble in thermostat or limit circuit. Check thermostat or limit 
wiring connections. 

5.  Jumper thermostat (T -T) 

terminals on R7184 

 
IMPORTANT 
First remove one thermostat 
lead wire. 

Burner does not start. 

Disconnect the line voltage power and open line switch. 
Check all wiring connections. 
Tighten any loose connections and recheck. 
If burner does not start, replace R7184 

 
Condition:  Burner starts then locks out on safety with indicator light flashing at 1 hz rate (1/2 second on, 1/2 
second off) 

Indicator light stops flashing. 

Go to Step 7. 

6.  Reset oil primary control 

by pushing in and 
releasing red reset button. 

Indicator light continues to 
flash at 1 Hz rate. 

Verify that the control is not in restricted mode. (See notes at 
end of this table.). If not in restricted mode, replace R7184 

Ignition is off 

Spark igniter could be defective. Check for line voltage at 
igniter terminals. If line voltage is present, replace R7484. 

Ignition is on. 

Go to Step 8. 

7. Listen for spark after 

burner turns on (after 2 
second delay). 

Ignition is on but no oil is 
being sprayed into the 
combustion chamber. 

Wait for “Valve ON” delay to complete. Check oil supply, and 
oil line valve. Check for filter blockage or seized oil pump. 

Indicator light is on until the 
control locks out and starts 
flashing during lockout. 

Replace R7184 

8.  Check indicator light after 

flame is established, but 
before oil primary control 
locks out. 

Indicator light stays off. 

Go to step 9. 

Burner locks out. 

Go to step 10. 

9.  Check cad cell sighting for 

view of flame. 

  Disconnect line voltage 

power and open line 
switch. 

 

Unplug cad cell and clean 
cad cell face with soft 
cloth. Check sighting for 
clear view of flame. 
Replace cad cell in socket. 

  Reconnect line voltage 

power and close line 
switch. 

 Start 

burner. 

Burner keeps running. 

System is OK. 

Continues on next page

 

Summary of Contents for P*LBX16F14501

Page 1: ...ER SET UP 11 TABLE A 3 BELT DRIVE BLOWER SET UP 11 TABLE A 4 DIRECT DRIVE BLOWER CHARACTERISTICS 12 TABLE A 5 BELT DRIVE BLOWER CHARACTERISTICS 12 WIRING DIAGRAM MODEL P LBX16F14501 13 WIRING DIAGRAM...

Page 2: ...f the furnace and related equipment shall be installed in accordance with the regulations of CAN CSA B139 Installation Code For Oil Burning Equipment as well as in accordance with local codes When ins...

Page 3: ...tility room two 2 ventilation openings must be provided connecting to a well ventilated space full basement living room or other room opening thereto but not a bedroom or bathroom One opening shall be...

Page 4: ...CE The flue pipe must not be routed through concealed space because it must be visually checked for signs of deterioration during the annual inspection and servicing The flue pipe must not pass throug...

Page 5: ...Must be handled by competent masonry contractor G Collection of soot at narrow space in flue opening Lower light on extension cord Clean out with weighted brush or bag of loose gravel on end of line H...

Page 6: ...s greater than 10 PSIG may cause damage to the shaft seal If the height of the oil stored in a tank above the oil burner exceeds 11 feet it may be necessary to use a pressure regulating device approve...

Page 7: ...ts are closed System switch must be on HEAT if so equipped 4 Re connect the thermostat wire If the thermostat is serving a combination heating and air conditioning system pay particular attention to p...

Page 8: ...auses soft and sooty flames resulting in soot build up throughout the heat exchanger passages Excess combustion air causes a bright roaring fire and high stack temperatures resulting in poor fuel effi...

Page 9: ...at exchanger If the plenum take off is unsuitable the supply air temperature may be measured within the first 18 inches of the first segment of supply air trunk duct If the temperature rise is outside...

Page 10: ...a long flexible plastic spout DO NOT OVER LUBRICATE Excess oil may result in premature electric motor failure Inspect the blower fan Clean it if necessary Oil Burner Maintenance Follow the instruction...

Page 11: ...up the chimney between burner cycles NOTE THE USE OF THIS CONTROL CAN OCCASIONALLY CAUSE POST COMBUSTION NOZZLE DRIP TABLE A 2 DIRECT DRIVE BLOWER SET UP BLOWER SET UP COOLING CAPACITY 0 20 in w c 0 5...

Page 12: ...5 BELT DRIVE BLOWER CHARACTERISTICS CFM External Static Pressure Inches water column Furnace Model Motor HP Motor FLA T Blower Blower Pulley Motor Pulley Turns Out 0 20 0 30 0 40 0 50 0 60 0 2274 2080...

Page 13: ...13 WIRING DIAGRAM MODEL P LBX16F14501 WIRING DIAGRAM MODEL P LBX20F19001...

Page 14: ...to spark for 10 sec a Provides continuous spark after flame is sensed to assure that burner remains lit b Turns on LED diagnostic light c Starts carryover timer i Flame and call for heat are monitore...

Page 15: ...rner Motor Solenoid Valve LED Diagnostic Light RETURNS TO IDLE STATE FLAME FLAME FLAME FLAME NO FLAME NO FLAME FLAME LOST FLAME LOST REMAINS IN IDLE STATE R7184 SEQUENCE of OPERATION LOCKOUT STATE R71...

Page 16: ...NG IMPORTANT Due to the potential hazard of line voltage only a trained experienced service technician should perform the troubleshooting procedure PRELIMINARY STEPS Check the diagnostic light for ind...

Page 17: ...ntrol If the indicator light turns off replace cad cell bracket assembly Burner starts Trouble is in thermostat circuit Check thermostat wiring connections If connections are clean and tight check the...

Page 18: ...6 Reset oil primary control by pushing in and releasing red reset button Indicator light continues to flash at 1 Hz rate Verify that the control is not in restricted mode See notes at end of this tabl...

Page 19: ...h time a call for heat is successfully completed To reset from RESTRICTED MODE press and hold the reset button for 30 seconds When the LED flashes twice the device has reset NOTE Disable function Pres...

Page 20: ...sence of light Ensure that room light is not leaking into the cad cell compartment see diagnostic light section or manually measure cad cell resistance No fuel oil Check fuel oil supply Check that all...

Page 21: ...Poor alignment between oil burner blast tube and fire pot Check alignment air tube should be centered with fire pot burner opening Oil burner head should be inch back from the inside surface of the f...

Page 22: ...erature rise Slow down blower fan if necessary Supply air temperature too cool Excessive duct losses Check supply air ductwork Seal leaky joints and seams Insulate ductwork if necessary Fan control fa...

Page 23: ...with a pair of awls or similar tool 5 Begin fastening the flue pipe flanges together from inside the blower section to the furnace section with the six 1 4 20 x 3 4 inch screws saved from the removal...

Page 24: ...t 21A Cleanout Gasket 2 per unit 22 Filter Air 20 x 20 x1 Permanent 23 Box Junction 24 Wire Harness Blower Direct Drive 25 Wire Harness Fan and LImit ITEM DESCRIPTION 26 Centre Fan 26A Relay Replaceme...

Page 25: ...ner Channel Wire 20 Access Panel Blower Door 20A Handle Door 21 Baffle Front Panel 22 Baffle Top Front Panel 23 Burner Assembly Oil 23A Motor Burner ITEM DESCRIPTION 23B Pump Oil 23C Ignitor Solid Sta...

Page 26: ...nt and or representative that can assist you Visit our website at www source1parts com for the following information 1 Search for a part or browse the catalog 2 Find a dealer or distributor 3 Customer...

Page 27: ...27 NOTES...

Page 28: ...ct to change without notice Printed in U S A 280200 UIM A 1206 Copyright by Unitary Products Group 2006 All rights reserved Supersedes 035 14289 001 Rev B 0605 Unitary 5005 Norman Products York OK Gro...

Reviews: