TABLE A-1: BECKETT OIL BURNER SET-UP
BECKETT AF SERIES OIL BURNERS
FURNACE
MODEL
OUTPUT
BTU/Hr.
BURNER
MODEL
NOZZLE
(Delavan)
PUMP
PRESSURE
FLOW
RATE
HEAD
STATIC
PLATE
130,000
AF65YB
1.10 / 70°A
100 PSIG
1.10 GPH
F6
2-3/4 in.
P*LBX16F14501
143,000
AF65YB
1.20 / 60°A
100 PSIG
1.20 GPH
F6
2-3/4 in.
168,000
AF81WF
1.50 / 70°B
100 PSIG
1.50 GPH
F16
2-3/4 in.
P*LBX20F19001
188,000
AF81WF
1.65 / 70°B
100 PSIG
1.65 GPH
F16
2-3/4 in.
In the United States, the R. W. Beckett “AF” Burner may be equipped with Beckett’s “Inlet Air Shut-Off”, Beckett Part No. AF/A 5861, to increase efficiency. It reduces the
amount of air passing through the oil burner, combustion chamber, breeching, etc. up the chimney between burner cycles.
NOTE: THE USE OF THIS CONTROL CAN OCCASIONALLY CAUSE POST COMBUSTION NOZZLE DRIP.
TABLE A-2: DIRECT DRIVE BLOWER SET-UP
BLOWER SET-UP
COOLING CAPACITY
0.20 in. w.c.
0.50 in. w.c.
FURNACE
OUTPUT
BTU/Hr.
BLOWER
MOTOR
HP
Speed Speed
Htg. CFM
Range
1
Tons
2
MOTOR
HP
Clg. CFM
Range
130,000
High
High
1332 - 1712
P*LBX16F14501
143,000
G10 DD
1/2
High
High
1465 - 1883
4
1/2
1065 - 1600
(1)
Heating Range values based on temperature rise. Upper values may exceed measured airflow values in Table A-3.
(2)
Nominal values only.
TABLE A-3: BELT DRIVE BLOWER SET-UP
Blower Set-Up
Cooling Capacity
0.20 in. W.C.
0.50 in. W.C.
Pulley Belt Pulley Belt
Furnace
Model
Blower Motor
Motor Blower
Motor Blower
Tons CFM
Range
3 1/2 x 5/8
7 x 3/4
4L430
3 1/2 x 5/8
7 x 3/4
4L430
P*LBX20F19001 G12 3/4
HP
3 1/2 x 5/8
7 x 3/4
4L430
3 1/2 x 5/8
7 x 3/4
4L430
4
1300 - 1535